Purpose
8058 is used for protection and isolation of distribution motors in electrical circuits with AC 50Hz and voltage of 380V or below.
8058 series explosion-proof small circuit breaker model meaning

The product guarantees reliable operation under the following conditions
a) Altitude not exceeding 2000m;
b) The ambient air temperature shall not be higher than+40 ℃ and not lower than -20 ℃;
c) The relative humidity of the surrounding air is not greater than 95% (at+25 ℃);
d) During normal operation, explosive gas mixtures of Class IIC T5, T6 and below may occur in places;
e) In places without rain or snow invasion;
f) A place that can prevent water and other liquids from entering;
g) Places without significant shaking and impact vibration;
h) The pollution level is level 3;
i) The installation category is Class III;
Technical data of 8058 series explosion-proof miniature circuit breaker
The work schedule is an 8-hour work schedule;
The rated short-circuit breaking capacity is 6KA;
The maximum cross-sectional area of the connecting wire of the explosion-proof circuit breaker is 10m ㎡;
The explosion-proof circuit breaker adopts explosion-proof and rubber sealed structure, with explosion-proof markings of Exd Ⅱ CT5 and Exd Ⅱ CT6;
The agreed heating current of the explosion-proof circuit breaker is shown in Table 1;
Table 1 Agreed heating current
|
Temperature group T |
T5 |
T6 |
|
Current A |
20,25,30,401) |
1,3,6,10,16 |
The rated working voltage Ue of the explosion-proof circuit breaker is shown in Table 2, with a rated frequency of 50Hz.
Table 2 Rated working voltage
|
U6 |
380V |
220V |
|
Overload characteristics |
B. C and D B,C and D |
B and C B and C |
|
polar number |
2P,3P,3P+N |
1P+N,2P |
The rated current of the explosion-proof circuit breaker is shown in Table 3
Table 3 Rated Current
|
Rated current A |
1,3,6,10,16 |
20,15,30,401) |
|
Temperature Class |
T6 |
T5 |
Note: 1) is an explosion-proof isolator
Explosion proof circuit breakers can also be used for limited motor protection with a fixed rated current of 16A or less, and their breaking capacity meets the requirements of Table 4.
Table 4 Switching Capacity
|
Usage category |
On-off conditions |
|
AC-3 |
1C/1e |
Ur/Ue |
COS Ф |
|
eight |
one point zero five |
zero point four five |
The type, current range, and time of the thermal release of the explosion-proof circuit breaker are specified in Table 5.
Table 5 Tripping Current
|
Types of Warm Release Devices |
Tripping current value |
tripping time |
|
B |
>3In~5In |
3In≥0.1s 5In<0.1s |
|
C |
>5In~10In |
5In≥0.1s 10In<0.1s |
|
D |
>10In~20In |
10In≥0.1s 20In<0.1s |