Product name: GW22B-252D(G)252kV Outdoor high-voltage AC isolation switch
specification: GW22B-252D(G)252kV Outdoor high-voltage AC isolation switch
  Zoom Zoom in on the image
Category: High voltage electrical appliances -- Outdoor isolation switch
Column tabs 
Price: factory price
Brand: Shanghai
Place of Origin: China
Column tabs 
Available Quantity: batch
delivery cycle: Spot goods (or inquire by telephone)
tabs
  Shanghai Beiyuan Industry and Trade Co.,Ltd
+86-21-66770508
+86-13916500500

Email 91way@163.com
Wechat 13916500500(Wechat)


GW22B-252D(G)252kV Outdoor high-voltage AC isolation switchDetailed product description:Column tabs
GW22B-252D (G) type outdoor high-voltage transmission equipment with a three-phase AC frequency of 50Hz is used to disconnect or connect high-voltage lines under no-load conditions, in order to switch high-voltage lines, change operating modes, and safely isolate high-voltage electrical equipment such as busbars and circuit breakers for maintenance.
This product is a single column vertical fracture deflection type and can be equipped with JW10-252 grounding switch. The isolation switch adopts SRCJ3 type motor operating mechanism three pole linkage operation; The grounding switch adopts SRCS1 type manual operation mechanism with three pole linkage operation.

The GW22B-252D (G) 252kV outdoor high-voltage AC isolation switch complies with standards such as GB1985-2004 "High Voltage AC Isolation Switches and Grounding Switches", GB11022-1999, DL/T593-2006 "Common Technical Requirements for High Voltage Switchgear and Control Equipment Standards", DL/T486-2000 "Technical Conditions for Ordering AC Isolation Switches and Grounding Switches", and meets the relevant regulations on ordering high-voltage isolation switches issued by State Grid Corporation of China for improvement. And through seismic resistance calculation analysis with a seismic intensity of 9 degrees.

project
Unit
Parameters
rated voltage
kV
two hundred and fifty-two
Rated insulation level(1)
a) 1-minute power frequency withstand voltage (effective value)
kV
to the ground
four hundred and sixty
kV
fracture
five hundred and thirty
b) Rated lightning impulse withstand voltage (peak)
kV
to the ground
one thousand and fifty
kV
fracture
one thousand and two hundred
rated frequency
Hz
fifty
rated current
A
1600           2000  2500  3150
Rated short-time withstand current
kA
40                    50
Rated peak withstand current
kA
100                   125
Rated short-circuit duration
s
three
Rated terminal mechanical load
Horizontal and vertical loads
N
two thousand
Horizontal lateral load
N
one thousand and five hundred
vertical force
N
one thousand two hundred and fifty
Isolation switch busbar conversion current opening and closing capability
300V, 1600A, 100 times
Grounding switch induced current opening and closing capability
1) Electromagnetic induction current (current/voltage)
A/kV
160/15(2) (80/2)
2) Static induced current (current/voltage)
A/kV
10/15(2) (3/12)
3) Opening and closing times
time
ten
Isolation switch low current opening and closing capability
capacitive current
A
one
Inductive current
A
zero point five
Rated contact area
Longitudinal displacement of supporting wire
150/200 (hard wire/soft wire)
Horizontal total offset
150/500 (hard wire/soft wire)
vertical offset
150/250 (hard wire/soft wire)
mechanical life
time
two thousand
creepage distance
mm
6300     7812
Human operated mechanism
model
SRCS1
Control circuit voltage
V
AC220
Electric motor operating mechanism
model
SRCJ3
Motor voltage
V
AC380
Control circuit voltage
V
AC220
Opening and closing time
s
10±1
output angle
135°
unipolar weight
not grounded
kg
six hundred
grounding
kg
six hundred and thirty
Note: (1) This product belongs to the high-altitude (G) type, and the insulation test is assessed at an altitude of 2000 meters, with a correction factor of k=1.13; If the insulation level is set at 395 kV, it can be used in areas with an altitude of 2800 meters.
(2) The parameters are specified as Class B values in DL/T486-2000, and arc ignition devices must be installed; The values in parentheses are specified for Class B in GB1985-2004.

GW22B-252D(G)252kV Outdoor high-voltage AC isolation switch