| Product name: | LENJH8-220W type digital photoelectric current transformer | ||||||
| specification: | ![]() |
||||||
| Category: | High voltage electrical appliances -- electronic instrument transformer | ||||||
| Price: | factory price | ||||||
| Brand: | Shanghai | ||||||
| Place of Origin: | China | ||||||
| Available Quantity: | batch | ||||||
| delivery cycle: | Spot goods (or inquire by telephone) | ||||||
|
|||||||
1、 Overview (Description)
LENJH8-220W digital photoelectric current transformer adopts digital technology, advanced photoelectric technology, and integrates the essence of domestic high-voltage electrical equipment technology to develop a new type of high-voltage current measuring device. It can be used to measure the current in high-voltage power supply systems for metering and protection purposes. Suitable for use in power systems with a rated frequency of 50Hz or 60Hz and a rated voltage of 110kV for energy metering, current measurement, and relay protection. This product complies with the standards of IEC60044-8:2002 and GB/T20840 · 8-2007 "Electronic Current Transformers".
3、 Structure Introduction (Construction)
1. The LENJH8-220W digital photoelectric transformer is a new type of electronic current transformer. It is different from traditional electromagnetic current transformers, as it adopts optoelectronic isolation, data digitization, and optical communication technology. The use of highly reliable electrical insulation design greatly enhances reliability.
2. It is also different from photoelectric current transformers based on Faraday magneto-optical effect and Kerr electro-optic effect. Its current signal sensor is a low-energy current transformer and a Rogowski coil. The current signal is converted into a digital signal at high potential and transmitted to low potential through optical fiber. So the measurement accuracy is high, and the resistance to vibration, external temperature changes, electromagnetic interference, and operating life are all guaranteed.
3. In this device, the power supply at high potential is an important technological innovation. This device adopts multiple energy supply technologies such as low potential laser power supply and high potential energy extraction, and the product has high operational reliability.
4. The insulation column of the LENJH8-220W digital photoelectric transformer adopts a silicone rubber outer sheath umbrella skirt, which is a pillar type. Lightweight, simple, and lightweight structure; Has good anti pollution ability and high reliability.
4、 Technical parameters
1. Rated insulation level: 252/460/1050kV
2. The partial discharge level complies with the GB/T20840 · 8-2007 standard for electronic current transformers. (The conditions of the partial discharge test according to GB/T20840·8-2007《electronic current transformer》will be fulfilled without exception.)
3. If users have other technical requirements, they can contact our factory. (If the customer has other requirement for technology, they can contact our factory.)
4. Technical data form:
Table 1: Rated primary current and rated dynamic and thermal current
|
Rated primary current Rated
primary
current
(A) |
Rated short-time thermal current (Ith)
Rated short time thermal current(kA/s) |
Rated dynamic stability current (Idyn)
Rated dynamic current(kA) |
|
fifty |
31.5/1 |
eighty |
|
sixty |
31.5/1 |
eighty |
|
seventy-five |
31.5/1 |
eighty |
|
one hundred |
31.5/1 |
eighty |
|
150, 200 |
31.5/3 |
eighty |
|
300-3150 |
50/3 |
one hundred and twenty-five |
|
one |
Maximum voltage of equipment
Highest voltage of equipment |
252kV |
|
two |
Rated primary current
Rated primary current |
50~3150A |
|
three |
Rated secondary voltage (measurement level)
Rated secondary voltage for measurement |
1.5V,4V |
|
four |
Rated secondary voltage (protection level)
Rated secondary voltage for protection |
150mV (hollow coil)
150mV(air-core coil) |
|
five |
Rated secondary voltage (protection level)
Rated secondary voltage for protection |
225mV (iron core coil)
225mV(core type coil) |
|
six |
Rated output digital quantity (measurement level)
Rated digital output for measurement |
0x2D41 |
|
seven |
Rated output digital quantity (protection level)
Rated digital output for protection |
0x01CF/0x00E7 |
|
eight |
Measurement level accuracy level
Accuracy class for measurement |
0.2, 0.2S class |
|
nine |
Protection level accuracy level
Accuracy class for protection |
5TPE (hollow coil)
5TPE(air-core coil) |
|
ten |
Protection level accuracy level
Accuracy class for protection |
5P30 (iron core coil)
5P30(core type coil) |
|
eleven |
rated frequency
Rated frequency |
50Hz (or 60Hz) |
|
twelve |
rated load
Rated burden |
2kΩ,20kΩ,2MΩ |
|
thirteen |
Rated symmetry of transient characteristics
Short circuit current multiple |
thirty |
|
fourteen |
Rated primary time constant
Rated primary time constant |
100mS |
|
fifteen |
Rated wake-up time
Rated wake-up time |
0 |
|
sixteen |
ambient temperature
Ambient temperature |
-40℃~+80℃ |
|
seventeen |
Environmental pollution level
Pollution class |
Ⅳ |
|
eighteen |
Wire connection method
Connection method of wires |
Through type, connecting type
penetrating type、point-type connection |