HomeYour location:HomeHigh voltage electrical appliancesHigh voltage isolation switchOutdoor isolation switch → GW5-40.5D(W)/630 Outdoor AC High Voltage Isolation Switch
Column tabs 
Product name: GW5-40.5D(W)/630 Outdoor AC High Voltage Isolation Switch
specification: GW5-40.5D(W)/630 Outdoor AC High Voltage Isolation Switch
  Zoom Zoom in on the image
Category: High voltage electrical appliances -- Outdoor isolation switch
Column tabs 
Price: factory price
Brand: Shanghai
Place of Origin: China
Column tabs 
Available Quantity: batch
delivery cycle: Spot goods (or inquire by telephone)
tabs
  Shanghai Beiyuan Industry and Trade Co.,Ltd
+86-21-66770508
+86-13916500500

Email 91way@163.com
Wechat 13916500500(Wechat)


GW5-40.5D(W)/630 Outdoor AC High Voltage Isolation SwitchDetailed product description:Column tabs
The GW5 series outdoor AC isolation switch is an outdoor high-voltage electrical equipment with an AC frequency of 52Hz, with rated voltage levels of 40.5kV, 72.5kV, and 126kV. It is used for opening and closing high-voltage lines under no-load conditions, as well as for electrically isolating high-voltage busbars, circuit breakers, and other electrical equipment under maintenance from live high-voltage circuits. It can also be used for opening and closing small capacitor or inductor currents.

GW5-40.5D (W)/630 outdoor AC high voltage isolation switch meets the relevant provisions of GB1985 "AC High Voltage Isolation Switches and Grounding Switches", IEC60129 "AC Isolation Switches and Grounding Switches", and GB/T11022 "Common Technical Requirements for High Voltage Switchgear and Control Equipment Standards".
GW5-40.5D (W)/630 Outdoor AC High Voltage Isolation Switch Model Description
Environmental conditions for use:
+Altitude: not exceeding 3000m;
+Surrounding air temperature: upper limit 40 ℃, lower limit -25 ℃;
+Wind speed not exceeding 35m/s;
+The seismic intensity shall not exceed 8 degrees;
+The pollution level shall not exceed level III;
+The thickness of ice cover shall not exceed 10mm;
+The installation site should be free from flammable, explosive hazards, chemical corrosion, and severe vibrations.

Classification
Model number
rated
voltage
(V)
rated
current
(A)
disconnecting switch
grounding switch
grounding
kind
peak
tolerance
current
(kA)
short-term
tolerance
current
(kA)
peak
tolerance
current
(kA)
short-term
tolerance
current
(kA)
Type I
Type I
Type I
Type II
Type I
Type II
General type
(Anti fouling type)
GW5
HGW5
-40.5
(D、DW)
-72.5Ⅱ
-126
forty point five
seventy-two point five
one hundred and twenty-six
six hundred and thirty
fifty
20 (4s)
fifty
eighty
twenty
(4s)
thirty-one point five
(4s)
not grounded
Single grounding
Double grounding
one thousand
one thousand two hundred and fifty
eighty
31.5 (4s)
one thousand and six hundred
31.5 (4s)
two thousand


Structure Introduction:
Each isolation switch consists of two pole insulators, each fixed on a base at an angle of 50 °The V-shaped structure mainly consists of the following parts: base part, post insulator, terminal block part, contact part, grounding knife, grounding static contact, terminal block, etc.
This isolation switch is divided into three types: ungrounded, single grounded, and double grounded. There is a mechanical interlock between the spindle and the grounding knife, and it is equipped with an auxiliary switch. There are two operation modes for the switch: manual and electric.

GW5-40.5D (W)/630 Outdoor AC High Voltage Isolation Switch Appearance and Installation Dimensions:

Installation dimension diagram of GW5-40.5D (W)/630 outdoor AC high voltage isolation switch
Figure 1 GW5-40.5 (126) D/630 Single pole Isolation Switch

GW5-40.5D (W)/630 Outdoor AC High Voltage Isolation Switch Structure Diagram
Installation Diagram of GW5-40.5D (W)/630 Outdoor AC High Voltage Isolation Switch

Figure 2 Installation diagram of switch three pole linkage

Model number
Rated voltage (kV)
L1 (mm)
L2 (mm)
L3 (mm)
L4 (mm)
L5 (mm)
L1 (mm)
GW5-110
one hundred and twenty-six
~2000
~2800
~1473
~1569
~1533
~1362
GW5-35
forty point five
~1200
~1600
~830
~1000
~845
~700

GW5-40.5D (W)/630 Outdoor AC High Voltage Isolation Switch Mechanism Diagram
GW5-40.5D (W)/630 Outdoor AC High Voltage Isolation Switch Distribution Diagram
GW5-40.5D (W)/630 outdoor AC high voltage isolation switch phase to phase distance

GW5-40.5D (W)/630 Outdoor AC High Voltage Isolation Switch

GW5-40.5D(W)/630 Outdoor AC High Voltage Isolation Switch
  • Related product tags  Related Products:
Product Category
All product information on this website is translated by Baidu machine translation, which may not be completely accurate and is only for reference