The ZGF DC high-voltage generator adopts an intermediate frequency voltage doubling circuit, applies PWM pulse width modulation technology and high-power IGBT devices. According to the theory of electromagnetic compatibility, special shielding, isolation, and grounding measures are adopted to achieve high regulation accuracy, simple operation, small size, light weight, and convenience for the power department. The enterprise power department conducts DC high voltage tests on equipment such as zinc oxide lightning arresters, power cables, generators, transformers, and switches.
Technical parameters of ZGF DC high voltage generator
1. Voltage measurement error: 1.0% (full scale) ± 1 word
2. Current measurement error: 1.0% (full scale) ± 1 word
3. Overvoltage setting error: ≤ 1.0%
4. 0.75 Switching error: ≤ 0.5%
5. Ripple coefficient: ≤ 0.5%
6. Voltage stability: random fluctuations, changes in power supply voltage
±10%,≤0.5%
7. Working mode: intermittent use, rated load for 30 minutes
8. 1.1 times rated voltage usage: 10 minutes
9. Environmental temperature: -15 ℃~50 ℃ Relative humidity when the temperature is
Not exceeding 90% at 25 ℃ (no frost)
10. Altitude: below 2000 meters