P-05 series passive thermistor signal isolator input and output range
| code |
input |
code |
output |
| one |
CU50(-20℃-100℃) |
one |
Two wire output 4-20mA |
| two |
CU100(0-100℃) |
| three |
PT100(0-150℃) |
| four |
PT100(0-200℃) |
| five |
PT1000(0-400℃) |
| eight |
User specific parameters |
Technical specifications for the main P-05 series passive thermistor signal isolator
| Thermistor excitation current |
800uA |
| Output load resistance |
0-500Ω |
| precision |
±0.2%F.S |
| temperature coefficient |
<50ppm/℃ |
| Ambient temperature |
-10℃~+60℃ |
| insulation resistance |
Between input and output ≥ 100M Ω (500Vdc) |
| Insulation strength |
Between input and output ≥ 1500Vac/min |
| Two wire power supply |
24VDC (internal power supply for interface) |
Ordering instructions
Example of code indicating input and output signals: Input PT100 (0-200 ℃) output 4-20mA model P-0541
Product Features
Self powered 35mm DIN rail installation fixed terminal, bolted wiring input and output fully isolated
wiring diagram

block diagram

Overall dimensions