G-512 thermocouple signal distributor input and output range
| code |
input signal |
Please specify when placing an order Model of thermocouple (K.S.B et al.) |
| one |
0-400℃ |
| two |
0-600℃ |
| three |
0-800℃ |
| four |
0-1000℃ |
| five |
0-1200℃ |
| six |
0-1400℃ |
| seven |
0-1600℃ |
| eight |
User specific parameters |
| code |
Output signal 1 |
code |
Output signal 2 |
output impedance |
| A |
0-5V |
A |
0-5V |
≥10K |
| B |
1-5V |
B |
1-5V |
|
| C |
0-20mA |
C |
0-20mA |
≤500Ω |
| D |
4-20mA |
D |
4-20mA |
|
| H |
User specific parameters |
| When outputting as a single channel, output signal 2 is the default |
Main technical specifications of G-512 thermocouple signal distributor
| output impedance |
0—500Ω |
| response time |
<0.05s(0~90%)(TYP) |
| Bo??? pattern |
<10mVrms |
| Transmission error |
0.1% final value |
| temperature coefficient |
Measurement value of 50ppm/K per 100 Ω load |
| compressive strength |
100M Ω or above at 500VDC, 2000VAC/minute |
| Operating Temperature |
-10℃~+70℃ |
| Operating Humidity |
<90% RH (no condensed water) |
| Electricity??? source |
24VDC ± 10% or 110-265VAC |
| power consumption |
<2W |
| housing material |
Nylon PA.66 |
| Heavy??? quantity |
About 120 grams |
Ordering instructions
Example of code indicating input and output signals: Input 0-800 ℃ output signal 1:1-5VDC output signal 2:4-20 mA model G-5123BD
(Indicate thermocouple models K, S, B, etc.)
Product Features
Fixed terminal, bolt connection 35mm DIN rail mounted digital circuit, higher precision input/output/power/channel fully isolated cold end compensation, wire breakage alarm, non-linear processing
wiring diagram

block diagram

Overall dimensions