P01 Current Loop Isolation Module Input and Output Range
| input |
|
| input signal |
0(4)…20mA |
| operating current |
≤20mA |
| pressure drop |
≤2V |
| overload |
50mA,15V |
| output signal |
0(4)…20mA |
| load |
≤500Ω |
| response time |
approximately 10ms@500 Ω load |
| ripple |
≤10mVrms |
Main technical specifications
| Load error |
+0.05% F.S/100 Ω when the load is less than 250 Ω -0.05% F.S/100 Ω when the load is greater than 250 Ω |
| Accuracy |
0.1% final value (under load of 250 Ω) |
| temperature coefficient |
<50PPM/℃ |
| test voltage |
Between the input/output terminals of 2.5KV and 50HZ |
| Working voltage (insulation) |
Maximum 600VAC/DC |
| Electric shock protection |
Maximum 300VAC/DC |
| Ambient temperature |
Work transportation and storage -20℃~+70℃ -25℃~+85℃ |