Scope of application
The JK-908 intelligent flow integrator is used in conjunction with various flow sensors or transmitters, temperature sensors or transmitters, and pressure transmitters. The intelligent flow integrator can measure and display various flow parameters of liquids, steam, natural gas, general gases, etc., accumulate calculations, alarm control, transmission output, data acquisition, and communication.
Features
Intelligent flow integrator with full range automatic temperature and pressure compensation calculation, compensation method can be set arbitrarily
Linear integration and square root integration can be set arbitrarily
Display of multiple parameters including instantaneous flow rate, cumulative flow rate, temperature, and pressure
Small signal resection function, resection range 0-5% optional
The accumulated flow value of the intelligent flow integrator can be reset to zero through the panel buttons, and the reset operation can be locked
Power off protection function, the accumulated flow value can be maintained for more than 5 years after power failure, and all set values will be permanently maintained after power failure
The advanced modular structure of the intelligent flow integrator, combined with powerful instrument chips, makes function combination and system upgrade very convenient
Main technical indicators
Basic error: 0.5% FS or 0.2% FS ± 1 word
Resolution: 1/20000, 14 bit A/D converter
Display mode: dual row simultaneous display, the upper four digit digital tube displays instantaneous flow, and the lower eight digit digital tube displays cumulative flow. Sampling period: 0.5S
Alarm output: instantaneous flow limit alarm, relay output contact capacity AC220V/3A
Transmission output: 4-20mA, 0-10mA, 1-5V, 0-5V Accuracy: ± 0.3% FS
Communication output: Interface mode - isolated serial bidirectional communication interface RS485/RS422/RS232/modem
Baud rate -300~9600bps, freely set internally
Feed output: DC24V/50mA
Power supply: Switching power supply 85-265VAC, power consumption below 4W
Model Description
| Type spectrum |
Instructions |
| HB-908 |
|
Intelligent traffic integrator |
| Overall dimensions |
A |
|
Horizontal 160 × 80 × 125mm |
| A/S |
|
Vertical 80 × 160 × 125mm |
| B |
|
Method 96 × 96 × 110mm |
| controlled output |
B0 |
|
B0 has no alarm output, can be omitted |
| B1 |
|
Instantaneous flow upper limit alarm |
| B2 |
|
Instantaneous flow lower limit alarm |
| B3 |
|
Instantaneous flow upper and lower limit alarm |
| B4 |
|
Accumulated traffic limit alarm |
| B5 |
|
Accumulated flow lower limit alarm |
| B6 |
|
Accumulated flow upper and lower limit alarm |
| transmitter output |
X1 |
|
4-20mA output |
| X2 |
|
0-10mA output |
| X3 |
|
1-5V output |
| X4 |
|
0-5V output |
| communication output |
P |
|
Mini Printer |
| R |
|
Serial communication RS232 |
| S |
|
Serial communication RS485 |
| Power supply for transmitter distribution |
|
No feed output |
| V12 |
|
Equipped with DC12V power supply output |
| V24 |
|
Equipped with DC24V power supply output |
| power supply |
|
220VAC power supply |
| W |
|
DC24V power supply |
| Traffic input signal |
L1 |
|
Current: 4-20mA, 0-10mA, 0-20mA |
| L2 |
|
Voltage: 1-5V, 0-5V |
| L3 |
|
Pulse frequency: 0-10KHZ |
| Temperature input signal |
W1 |
Current: 4-20mA, 0-10mA, 0-20mA |
| W2 |
Voltage: 1-5V, 0-5V |
| W3 |
Thermal resistance: Pt100 |
| W4 |
Thermocouples: K, T, E |
| Pressure input signal |
Y1 |
Current: 4-20mA, 0-10mA, 0-20mA |
| Y2 |
Voltage: 1-5V, 0-5V |
Model example: HB-908AB3X1SV24L1W1Y1
HB-908 series intelligent flow integrator, with external dimensions of 160 × 80 × 125mm, instantaneous flow upper and lower limit alarm control output, 4-20mA instantaneous flow signal input, 4-20mA pressure signal input, 4-20mA temperature signal input, 4-20mA instantaneous flow transmission output, with RS485 isolated communication interface, DC24V feed output, power supply 220VAC