HomeYour location:Homeinstrumentation and metersElectrical instrumentspower meter → PF109 type power frequency electrical parameter measuring instrument
Column tabs 
Product name: PF109 type power frequency electrical parameter measuring instrument
specification: PF109 type power frequency electrical parameter measuring instrument
  Zoom Zoom in on the image
Category: instrumentation and meters -- power meter
Column tabs 
Price: factory price
Brand: Shanghai
Place of Origin: China
Column tabs 
Available Quantity: batch
delivery cycle: Spot goods (or inquire by telephone)
tabs
  Shanghai Beiyuan Industry and Trade Co.,Ltd
+86-21-66770508
+86-13901609058

Email 91way@163.com
Wechat 13901609058(Wechat)


PF109 type power frequency electrical parameter measuring instrumentDetailed product description:Column tabs
The PF109 power frequency electrical parameter measuring instrument can simultaneously measure three-phase voltage, three-phase current, three-phase active power, three-phase reactive power, total added power, phase, power factor, and frequency. Standard measurement of electrical energy can be achieved through unique digital/frequency conversion technology. This product adopts plasma display with RS232 interface, which can easily form an automatic measurement system. It has a wide range of voltage and current measurement, and the voltage range can be automatically switched.. It is currently one of the advanced instruments for measuring comprehensive performance of power frequency electrical parameters, and can be widely used in power departments, metrology departments, and laboratories as a 0.05 level and 0.1 level standard.

Main technical specifications of PF109 power frequency electrical parameter measuring instrument
1. Voltage range: 30V, 60V, 100V, 150V, 250V, 300V, 450V, 600V
Measurement accuracy: 3V-750V error ≤ 0.03% (reading) ± 0.02% (full scale)
2. Current range: 1A, 5A, 25A, 50A or 100A
Measurement accuracy: Range error of 5% -125% for each range is less than 0.03% (reading) ± 0.02% (full scale)
3. Power measurement range: 0-30000W
Accuracy of active and reactive power measurement: 0.05%
4. Phase measurement range: -180.0 °~+180.0 ° or 0 °~359.99 °
Phase measurement accuracy: 0.05 ° (current input ≥ 50% In voltage input>57V)
0.10 ° (current input ≥ 10% In, voltage input>20V)
5. Frequency measurement range: 45HZ~65Hz
Frequency measurement resolution: 0.001HZ Frequency measurement accuracy: 0.005HZ
6. Power factor measurement range: -1.0~+1.0
Accuracy of power factor measurement: 0.0005 Resolution of power factor measurement: 0.0001
7. Accuracy of active and reactive energy measurement: 0.05%
8. Distortion measurement range: 0.01%~100% Accuracy: 0.02% (relative to the main wave)
9. Harmonic measurement range: 0-21 times accuracy: 0.05% (relative to the main wave)
10. Working environment temperature: 5 ℃~40 ℃ Relative humidity: ≤ 85% Non corrosive gas
11. Size: 363mm × 270mm × 100mm
12. Whole machine weight: 4.5Kg

PF109 type power frequency electrical parameter measuring instrument