LVB-220W High Voltage Current Transformer
|
| Rated voltage kV |
two hundred and twenty |
| Rated insulation level kV |
252/460/1050 |
| Rated secondary current A |
5 (or 1) |
| Rated primary current A |
2 * 1250, 2 * 750, 2 * 1500 |
| Level combination |
B/B/B2/B2/0.2 |
| Secondary performance (protection level) |
2*1250/5 |
2*1250/1 |
2 * 750/5, 2 * 1500/5 |
2 * 750/1, 2 * 1500/1 |
| Grade B |
Full turn/tap vA |
40/25(50/25) |
30/20 |
50/30 |
30/20 |
| Accuracy Limit Factor (ALF) |
5P20(5P15) |
5P20 |
5P20 |
5P20 |
| B2 level
|
Full turn/tap vA |
60/30(50/25) |
40/25 |
60/30 |
40/25 |
| Accuracy Limit Factor (ALF) |
5P25(5P30) |
5P25 |
5P30 |
5P30 |
| Measurement level performance |
Full turn/tap vA |
60/30 |
40/20 |
60/30 |
40/20 |
| Instrument security factor (FS) |
five |
five |
five |
five |
| Short time thermal current kA/3s |
2*750A:31.5-50; Others: 40-63 |
| Dynamic stability current kA |
2*750A:80-125; Others: 100-160 |
| Product dielectric loss rate% |
Not more than 0.5%, zero screen to ground not more than 0.7% |
| Partial discharge pC |
Not greater than 10 (not greater than 5pC at 252kV or 220kV) |
| Creepage distance mm |
5040, 6300 |
| Oil weight/total weight kg |
200/850(880) |
| Altitude m |
Not exceeding 3000 |
| Terminal withstand load once |
horizontal direction |
4000N |
| Other directions |
4000N |