JC-9000 Type SF6 Density Relay Calibration InstrumentDetailed product description:

The JC-9000 SF6 density relay calibration instrument adopts precision imported parts. Through high-precision pressure sensors and high-precision A/D and D/A converters, combined with high-performance 32-bit ARM microcontrollers and TI's high-speed signal processing chips, it can automatically complete the calibration of SF6 density relays. It can accurately measure the pressure value at the current temperature when the signal is activated and automatically convert the standard pressure at any ambient temperature up to 20 ℃. It can automatically print test data and store it for future reference. The entire process does not require manual intervention and automatically identifies faults during the testing process, reflecting the "intelligent" characteristics of the instrument. The instrument has the characteristics of high precision, high stability, and high reliability.
Function and characteristics of SF6 density relay calibrator
1. Adopting a 32-bit high-speed microcontroller and TI's high-speed signal processing chip for detection and control, with a high degree of integration. Mechatronics design, high precision, good repeatability, and high reliability
2. Equipped with a monochrome LCD screen and a soft keyboard human-machine interface, the operation is simple, the interface is beautiful, and all parameters and statuses are clear at a glance
3. Automatically complete pressure measurement and 20 ℃ value conversion, thus achieving dynamic automatic compensation between pressure and temperature. And display the pressure and ambient temperature at the tested ambient temperature of 20 ℃. Thoroughly solved the problem of difficult on-site calibration of SF6 gas density relays
4. All testing processes are automatically completed by instruments without manual intervention, avoiding tedious manual air circuit adjustment operations
5. Printing test results in Chinese character report format and conducting intelligent analysis on the test results
6. It can store 50 test results simultaneously and has power-off data protection function, which can query and print previous test results at any time
7. During the verification process, no constant temperature chamber is required, and SF6 gas density relays and pressure gauges can be verified within any effective temperature range
8. Equipped with multiple types of transition joints, most density relays for switches can be verified on-site without disassembly
9. During the verification process, SF6 gas is not wasted, the testing cost is low, and there is no pollution to the environment
10. It has the function of online modification of system clock
11. It has the function of online modification of system pressure, which can be corrected on-site
12. The core components are imported and have reliable performance
13. Can simultaneously test one set of alarm signals and two sets of locking signals
14. This product is a portable tool that is easy to use and reliable. It is an essential equipment for verifying SF6 density relays
Technical parameters of JC-9000 SF6 density relay calibrator
1. Working voltage: AC220V, 50Hz
2. Instrument power: 50W
3. Instrument accuracy: 0.2 level
4. Pressure display resolution: 0.001MPa
5. Pressure calibration range: 0-1.0MPa
6. Environmental temperature display resolution: 0.1 ℃
7. Environmental temperature measurement range: -50 ℃ to 150 ℃
8. Working humidity: ≤ 90% RH
9. Verification objects: single alarm, single lock, single alarm single lock, single alarm double lock
10. Display mode: 320 × 240 graphic dot matrix monochrome LCD screen
11. Operation method: Soft keyboard key input
12. Printer type: high-speed micro printer
13. Printing method: Chinese character report printing
14. Storage capacity: capable of storing 50 test results simultaneously
15. Dimensions: Host 375 × 270 × 240mm3
Attachment box 400 × 370 × 200mm3
16. Display mode: pressure under the tested environment, equivalent pressure at 20 ℃
17. Instrument weight: 8Kg
Storage and transportation
The JC-9000 SF6 density relay calibrator is a precision electronic product that should be placed at a temperature of -30 to 70 ℃, a relative humidity of no more than 90%, and the air should not contain gases that can cause corrosion.
The transportation of the calibration instrument should avoid severe vibration and impact, and prevent rain and snow from soaking it.
Verification gas source: Due to the national security inspection department's prohibition on transportation, it can only be inflated at the user's location or test site (preferably at a professional inflation point, if there are no professional inflation conditions, it can be inflated by oneself)