The JF-2008 partial discharge detector has high detection sensitivity, a wide coverage range of sample capacitance, a wide range of applicable test samples, complete input units (detection impedance), and multiple frequency band combinations (nine types). After appropriate calibration, the partial discharge detector can directly read the discharge amount of the discharge pulse. The pointer type meter and digital meter display simultaneously, and the pointer type meter can conveniently select logarithmic or linear scale indication as needed. Widely applicable for measuring partial discharge of various high-voltage electrical products such as transformers, transformers, high-voltage switches, zinc oxide lightning arresters, power cables, etc., conducting type tests on products, and supervising insulation operation. This instrument is a practical partial discharge testing device widely used by power departments, manufacturers, and research institutes.
Technical specifications of JF-2008 partial discharge detector
1. The capacitance range of the testable product is 6PF to 250 μ F
2. Detection sensitivity (see Table 1)
3. Amplifier frequency band: ① Low end: 10kHz, 20kHz, 40kHz optional ② High end: 80kHz, 200kHz, 300kHz optional
4. Amplifier gain adjustment: Roughly adjust to six levels, with a gain of 20 ± 1 db between levels; finely adjust to a range>20db.
5. Time window:
① Window width: adjustable range of 15 ° to 150 °;
② Window position: Each window can rotate 0 ° to 170 °;
③ Two time windows can be opened separately or simultaneously.
6. Partial discharge detector discharge gauge:
① Pointer type header:
Logarithmic scale 1-10-100 error<± 5% (measured at full scale)
Linear scale 0-1000 error<± 5% (measured at full scale)
② Number header: with 3? LED digital display
0-100.0 error<± 5% (measured at full scale)
7. Elliptical Time Base:
① Frequency 50Hz, 100Hz, 150Hz, 200Hz, 400Hz.
② Elliptical rotation: With 30 ° as the first gear, it can rotate 120 °.
③ Display mode: ellipse - straight line.
④ The high-frequency time base ellipse can be adjusted to its normal size according to the input voltage (13-275V), with an intake power of less than 1 volt ampere.
8. Test voltmeter:
① Range: 100kV (expandable)
② Display: 3? Digital voltmeter indication
③ Accuracy: better than ± 5% (measured at full scale)
9. Internal and external zero standard function
10. Volume: 500 * 500 * 210 (width * depth * height) mm3
11. Weight: Approximately 18kg
|
Enter unit number |
Tuning capacitor |
unit |
Sensitivity (Micro Library)
(Asymmetric Circuit) |
|
one |
6-25-100 |
Micro method |
zero point zero two |
|
two |
25-100-400 |
Micro method |
zero point zero four |
|
three |
100-400-1500 |
Micro method |
zero point zero six |
|
four |
400-1500-6000 |
Micro method |
zero point one |
|
five |
1500-6000-25000 |
Micro method |
zero point two |
|
six |
0.006-0.025-0.1 |
microfarad |
zero point three |
|
seven |
0.025-0.1-0.4 |
microfarad |
zero point five |
|
eight |
0.1-0.4-1.5 |
microfarad |
one |
|
nine |
0.4-1.5-6.0 |
microfarad |
one point five |
|
ten |
1.5-6.0-25 |
microfarad |
two point five |
|
eleven |
6.0-25-60 |
microfarad |
five |
|
twelve |
25-60-250 |
microfarad |
ten |
|
7R |
resistance |
|
zero point five |
JF-2008 Partial Discharge Detector