RK9830N Three phase AC parameter testerDetailed product description:Column tabs
RK9830N Three phase AC Parameter Tester

1. High measurement accuracy, wide range, and fast speed.
2. It can display the voltage, current, and power of a certain phase in the three-phase system separately,
It can also display the voltage, current, and power of three phases simultaneously, with flexible operation.
3. Equipped with power (energy) display function (energy value has automatic power-off saving function).
4. It has communication function and displays all parameters of the three phases simultaneously through the PC screen,
Display parameters more comprehensively and intuitively.
5. The power-off memory function can remember the settings and data before the power-off.
6. It has data retention function, making observation and recording more convenient.
7. Equipped with energy clearing function, convenient for energy measurement.
8. Compact appearance, easy to carry and operate

RK9830N Three phase AC Parameter Tester Basic Parameters

1. Voltage: 0-600V ± 0.5%+01d
2. Current: 0-40A
3. Power: Single phase: 0-24KW Three phase: 0-41.5KW
4. Power: 0-1000KW/h
5. Power factor: -1-+1 ± 0.02%
6. Frequency: 45Hz-65Hz

name

voltage

current

Input circuit type

Floating input

Floating input

measurement range

0-600V

0-40A

Continuous maximum input

800V

45A

Instantaneous maximum input

1600V

60A

communication function

RS232 (DB9) interface (optional)

Measuring speed

2 times per second

test frequency

45Hz-65Hz (refers to the frequency that the tester can detect)

working environment

0℃ ——40℃  20RH —— 85RH

Insulation resistance and withstand voltage

Wiring terminals and enclosures:>5M Ω,>1.5KV (sinusoidal AC)

working power supply

AC 220V ±20%,50/60Hz,<10W


Table 2: Measurement Accuracy and Error

parameter

range

error

display resolution

voltage

0-600V

± (0.4% (reading)+0.1% (range)+1 digit)

0.1V

current

0-40A

1mA

Power (single-phase)

0-24KW (note)

1mW

Power (three-phase)

0-41.5KW (note)

merit

0-1000KWh

0.001KWh

power factor

-1 — +1

±0.02

zero point zero one

frequency

45Hz —— 65Hz

0.05Hz

0.01Hz