JBK, JBT, JBKG (JKY, JBL) span parallel groove line clamps are suitable for non load bearing splicing and branching of overhead power lines, with the characteristics of easy and flexible installation, and a wide range of applicable wires. The JBKG series copper aluminum span clamps use friction welding or brazing processes for users to choose from. The insulation cover is used in conjunction with the wire clamp to provide insulation protection.
Performance characteristics of insulation cover
Power frequency withstand voltage: ≥ 4kV withstand voltage for 1 minute without breakdown or flashover;
Insulation resistance:>1.0 × 1014 Ω Environmental temperature: -300C~900C
Climate resistance: Good performance after 1008 hours of artificial climate aging test
This insulation cover is suitable for overhead power lines of 10kV and below
JBK, JBT, JBKG (JKY, JBL) span parallel trench line clamp model specifications and technical parameters
| Product Name |
model |
Applicable wire nominal cross-section (mm)two) |
remark |
| Aluminum span parallel groove clamp |
JBK-4~35/2 |
16~35/4~16 |
Hangzhou type |
| JBK-10~70/2 |
10~70 |
| JBK-16~120/2 |
16~120 |
| JBK-16~120/3 |
16~120 |
| JBK-50~240/2 |
50~240 |
| JBK-50~240/3 |
50~240 |
| JBK-120~400/2 |
120~400 |
| JBK-120~400/3 |
120~400 |
| JBK-35~120 |
35~120 |
Shanghai type |
| JBK-95~300 |
95~300 |
| JBK-50~240D |
50~240 |
Northeast type |
| JBK-16~120 |
16~120 |
Beijing type |
| JBK-50~240 |
50~250 |
| Copper span parallel groove clamp |
JBT-16~120 |
16~120 |
|
| JBT-50~240 |
50~240 |
| Copper aluminum span parallel groove clamp |
JBKG-10~70 |
10~70 |
friction welding |
| JBKG-16~120 |
16~120 |
| JBKG-50~240 |
50~240 |
| JBKG-10~70Q |
10~70 |
Brazed type |
| JBKG-16~120Q |
16~120 |
| JBKG-50~240Q |
50~240 |
Note:
1. The meaning of the letters and numbers in the table for the model is: J represents the connecting pipe; Y represents a circle; The number represents the nominal area of the applicable wire, and the additional letter YL represents the weather resistant insulated cable;
2. When used for a low voltage of 1kV, the complete set includes one aluminum tube, one 1kV heat shrink tube, and one hot melt adhesive. When used for a high voltage of 10kV, the complete set includes one aluminum tube, one 10kV heat shrink tube, one 10kV stress tube, and one hot melt adhesive.
3. According to user needs, it can also be used in conjunction with shrink tubing for easier installation.