| Product name: | JCZ5-7.2KV series vacuum contactor | ||||||
| specification: | ![]() |
||||||
| Category: | High voltage electrical appliances -- Vacuum Contactor Switch | ||||||
| Price: | factory price | ||||||
| Brand: | Shanghai | ||||||
| Place of Origin: | China | ||||||
| Available Quantity: | batch | ||||||
| delivery cycle: | Spot goods (or inquire by telephone) | ||||||
|
|||||||
|
Performance parameter model parameter name |
160A |
250A |
400A |
630A |
|
Rated working voltage (KV) |
seven point two |
seven point two |
seven point two |
seven point two |
|
Rated working current (A) |
one hundred and sixty |
two hundred and fifty |
four hundred |
six hundred and thirty |
|
Rated connection capacity (A/100 times) |
one thousand and six hundred |
two thousand and five hundred |
four thousand |
six thousand and three hundred |
|
Rated breaking capacity (A/25 times) |
one thousand two hundred and eighty |
two thousand |
three thousand and two hundred |
five thousand |
|
Ultimate breaking capacity (A/3 times) |
four thousand |
four thousand |
five thousand |
six thousand and three hundred |
|
Fracture frequency withstand voltage (KV) |
thirty-two |
thirty-two |
thirty-two |
thirty-two |
|
Phase to phase and phase to ground power frequency withstand voltage (KV) |
thirty-two |
thirty-two |
thirty-two |
thirty-two |
|
Lightning impulse withstand voltage (KV) |
sixty |
sixty |
sixty |
sixty |
|
Main circuit contact resistance (μ Ω) |
≤ 200 |
≤ 200 |
≤ 200 |
≤ 200 |
|
Rated operating frequency (times/h) |
six hundred |
six hundred |
six hundred |
six hundred |
|
Mechanical locking operation frequency (times/h) |
sixty |
sixty |
sixty |
sixty |
|
Mechanical lifespan (10000 cycles) |
one hundred |
one hundred |
one hundred |
one hundred |
|
Mechanical lock lock lifespan (10000 cycles) |
thirty |
thirty |
thirty |
thirty |
|
Contact terminal pressure (N) |
>100 |
>100 |
>150 |
>150 |
|
Contact opening distance (mm) |
5±0.5 |
5±0.5 |
5±0.5 |
5±0.5 |
|
Overtravel (mm) |
1.5 + 0.5 |
1.5 + 0.5 |
1.5 + 0.5 |
1.5 + 0.5 |
|
Weight (Kg) |
twenty-five |
twenty-five |
twenty-five |
twenty-five |
2. Control circuit
2.1. Control voltage Ua: AC or DC 110V, 220V, 380V, or customized according to user requirements.
2.2. Control power: Start<900W and maintain<30W. Machine protection mode: Close<800W, Open<700W.
2.3. Power frequency withstand voltage: 2KV.
3. Auxiliary circuit
3.1. Auxiliary contacts: The conventional products for providing auxiliary contacts for users are two normally open and two normally closed; Up to four normally open and five normally closed. Mechanical remains at two normally open and three normally closed; More touchpoints can be customized.
3.2. Contact capacity: AC380V 6A; AC220V 10A 。
3.3. Loop contact resistance ≤ 0.1 Ω
3.4. Power frequency withstand voltage: 2KV
4. Action characteristics
4.1. Opening and closing time ≤ 120ms.
4.2. Three phase synchronization time ≤ 2ms.
4.3. Closing bounce time ≤ 5ms.
4.4. Minimum pull in voltage ≤ 85% Ua. 10% Ua ≤ Maximum release voltage ≤ 75% Ua.