Product name: JCZ1-12KV series single pole high-voltage AC vacuum contactor
specification: JCZ1-12KV series single pole high-voltage AC vacuum contactor
  Zoom Zoom in on the image
Category: High voltage electrical appliances -- Vacuum Contactor Switch
Column tabs 
Price: factory price
Brand: Shanghai
Place of Origin: China
Column tabs 
Available Quantity: batch
delivery cycle: Spot goods (or inquire by telephone)
tabs
  Shanghai Beiyuan Industry and Trade Co.,Ltd
+86-21-66770508
+86-13916500500

Email 91way@163.com
Wechat 13916500500(Wechat)


JCZ1-12KV series single pole high-voltage AC vacuum contactorDetailed product description:Column tabs
JCZ1-12KV series single pole high-voltage AC vacuum contactor features:
Reasonable structure, small size, and space saving.
Adopting a dual coil electromagnetic system, the action force coordination characteristics are superior to those of a single coil, and the coil power is small with low temperature rise.
The position of the control terminal can be set according to user requirements for easy wiring.

Main performance parameters of JCZ1-12KV series single pole high-voltage AC vacuum contactor

Performance parameter model parameter name

160A

250A

400A

630A

Rated working voltage (KV)

7.2/12

7.2/12

7.2/12

7.2/12

Rated working current (A)

one hundred and sixty

two hundred and fifty

four hundred

six hundred and thirty

Rated connection capacity (A/100 times)

one thousand and six hundred

two thousand and five hundred

four thousand

six thousand and three hundred

Rated breaking capacity (A/25 times)

one thousand two hundred and eighty

two thousand

three thousand and two hundred

five thousand

Ultimate breaking capacity (A/3 times)

four thousand

four thousand

five thousand

six thousand and three hundred

Fracture frequency withstand voltage (KV)

32/42

32/42

32/42

32/42

Inter phase ground frequency withstand voltage (KV)

32/42

32/42

32/42

32/42

Main circuit contact resistance (μ Ω)

≤ 200

≤ 200

≤ 200

≤ 200

Mechanical lifespan (10000 cycles)

three hundred

three hundred

three hundred

three hundred

Electrical lifespan (10000 cycles)

thirty

thirty

thirty

thirty

Rated operating frequency (times/h)

six hundred

six hundred

six hundred

six hundred

Contact terminal pressure (N)

>100

>100

>150

>150

Contact opening distance (mm)

5/6±0.5

5/6±0.5

5/6±0.5

5/6±0.5

Overtravel (mm)

1.5+0.5

1.5+0.5

1.5+0.5

1.5+0.5

Weight (Kg)

10/12

10/12

10/12

11/13


Control and auxiliary circuits
a. Control voltage: AC or DC 110V, 220V, 380V or customized by the user.
b. Control power: < 700W/30W
C. Auxiliary contacts: The maximum number of auxiliary contacts used by users is four normally open and three normally closed.
d. Contact capacity: AC380 5A

JCZ1-12KV series single pole high-voltage AC vacuum contactor

JCZ1-12KV series single pole high-voltage AC vacuum contactor
Product Category