HomeYour location:HomePump valve fittingsPump productsfire pump → XBD-W type horizontal fire pump
Column tabs 
Product name: XBD-W type horizontal fire pump
specification: XBD-W type horizontal fire pump
  Zoom Zoom in on the image
Category: Pump valve fittings -- fire pump
Column tabs 
Price: factory price
Brand: Shanghai
Place of Origin: China
Column tabs 
Available Quantity: batch
delivery cycle: Spot goods (or inquire by telephone)
tabs
  Shanghai Beiyuan Industry and Trade Co.,Ltd
+86-21-66770508
+86-13916950330

Email 91way@163.com
Wechat 13916950330(Wechat)


XBD-W type horizontal fire pumpDetailed product description:Column tabs
Overview

The XBD-W fire pump is a horizontal, single-stage, multi-stage, and segmented structure, which is the latest energy-saving series product developed and produced. Its performance parameters and technical indicators meet relevant standards, and it has significant advantages such as high efficiency, low operating noise, good anti cavitation performance, reasonable structure, and long service life.

The XBD-W fire pump series has five varieties and over 40 specifications, with a rated flow range of 5-40L/S, a pressure range of 0.18-2.0MPa, a matching power range of 2.2-180KW, and a diameter range of ф 50-150mm. The XBD-W fire pump set can be used to transport clean water without solid particles and its physical and chemical properties
Used for liquids similar to water. Mainly used for boosting water supply in fire protection systems, it can also be applied to water supply and drainage in factories and mines, boosting water supply in high-rise buildings, remote water supply, heating, bathrooms, boiler cooling and heating water circulation boosting, air conditioning and refrigeration system water supply, and equipment matching.

Purpose

The XBD-W series fire specific pump is suitable for pressurized water supply in fire pipelines. Used for pressurized transportation of clean water or other liquids with physical and chemical properties similar to clean water. The temperature of the medium used does not exceed 80 ℃, suitable for industrial and urban water supply and drainage, high-rise building pressurized water supply, garden sprinkler irrigation, long-distance water supply, heating, bathroom and other cold and warm water circulation pressurization and equipment matching.

Model meaning

Model Description of XBD-W Horizontal Fire Pump

Performance Parameter Table

model

traffic
Q
(L/S)

Pressure
P
(MPa)

rotation speed
n
(r/min)

efficiency
n
(%)

power
N
(KW)

Required cavitation allowance
(NPSH) r
( m )

XBD1.8/5-50W

five

zero point one eight

one thousand four hundred and fifty

sixty-five

two point two

three point two

XBD2.7/5-50W

five

zero point two seven

one thousand four hundred and fifty

sixty-five

three

three point two

XBD3.6/5-50W

five

zero point three six

one thousand four hundred and fifty

sixty-five

four

three point two

XBD4.5/5-50W

five

zero point four five

one thousand four hundred and fifty

sixty-five

five point five

three point two

XBD5.4/5-50W

five

zero point five four

one thousand four hundred and fifty

sixty-five

five point five

three point two

XBD6.3/5-50W

five

zero point six three

one thousand four hundred and fifty

sixty-five

seven point five

three point two

XBD7.2/5-50W

five

zero point seven two

one thousand four hundred and fifty

sixty-five

seven point five

three point two

XBD8.1/5-50W

five

zero point eight one

one thousand four hundred and fifty

sixty-five

seven point five

three point two

XBD2.3/10-75W

ten

zero point two three

one thousand four hundred and fifty

sixty-eight

five point five

three

XBD3.4/10-75W

ten

zero point two four

one thousand four hundred and fifty

sixty-eight

seven point five

three

XBD4.6/10-75W

ten

zero point four six

one thousand four hundred and fifty

sixty-eight

eleven

three

XBD5.5/10-75W

ten

zero point five five

one thousand four hundred and fifty

sixty-eight

eleven

three

XBD6.9/10-75W

ten

zero point six nine

one thousand four hundred and fifty

sixty-eight

fifteen

three

XBD8.0/10-75W

ten

zero point eight zero

one thousand four hundred and fifty

sixty-eight

fifteen

three

XBD9.2/10-75W

ten

zero point nine two

one thousand four hundred and fifty

sixty-eight

eighteen point five

three

XBD10.3/10-75W

ten

one point zero three

one thousand four hundred and fifty

sixty-eight

eighteen point five

three

XBD2.9/20-100W

twenty

zero point two nine

one thousand four hundred and fifty

seventy-two

eleven

three point five

XBD4.3/20-100W

twenty

zero point four three

one thousand four hundred and fifty

seventy-two

fifteen

three point five

XBD5.8/20-100W

twenty

zero point five eight

one thousand four hundred and fifty

seventy-two

twenty-two

three point five

XBD7.2/20-100W

twenty

zero point seven two

one thousand four hundred and fifty

seventy-two

thirty

three point five


Performance parameter table of XBD-W horizontal fire pump

model

traffic
Q
(L/S)

Pressure
P
(MPa)

rotation speed
n
(r/min)

efficiency
n
(%)

power
N
(KW)

Required cavitation allowance
(NPSH) r
( m )

XBD8.6/20-100

twenty

zero point eight six

one thousand four hundred and fifty

seventy-two

thirty

three point five

XBD10.1/20-100

twenty

one point zero one

one thousand four hundred and fifty

seventy-two

thirty-seven

three point five

XBD11.5/20-100

twenty

one point one five

one thousand four hundred and fifty

seventy-two

forty-five

three point five

XBD13.0/20-100

twenty

one point three zero

one thousand four hundred and fifty

seventy-two

forty-five

three point five

XBD4.2/25-125

twenty-five

zero point four two

one thousand four hundred and fifty

seventy-three

twenty-two

three point five

XBD6.3/25-125

twenty-five

zero point six three

one thousand four hundred and fifty

seventy-three

thirty

three point five

XBD8.4/25-125

twenty-five

zero point eight four

one thousand four hundred and fifty

seventy-three

forty-five

three point five

XBD10.5/25-125

twenty-five

one point zero five

one thousand four hundred and fifty

seventy-three

fifty-five

three point five

XBD12.6/25-125

twenty-five

one point two six

one thousand four hundred and fifty

seventy-three

seventy-five

three point five

XBD14.7/25-125

twenty-five

one point four seven

one thousand four hundred and fifty

seventy-three

seventy-five

three point five

XBD16.8/25-125

twenty-five

one point six eight

one thousand four hundred and fifty

seventy-three

ninety

three point five

XBD18.9/25-125

twenty-five

one point eight nine

one thousand four hundred and fifty

seventy-three

ninety

three point five

XBD5.8/45-150

forty-five

zero point five eight

one thousand four hundred and fifty

seventy-six

forty-five

three

XBD8.7/45-150

forty-five

zero point eight seven

one thousand four hundred and fifty

seventy-six

seventy-five

three

XBD11.6/45-150

forty-five

one point one six

one thousand four hundred and fifty

seventy-six

ninety

three

XBD14.5/45-150

forty-five

one point four five

one thousand four hundred and fifty

seventy-six

one hundred and ten

three

XBD17.4/45-150

forty-five

one point seven four

one thousand four hundred and fifty

seventy-six

one hundred and thirty-five

three

XBD20.3/45-150

forty-five

two point zero three

one thousand four hundred and fifty

seventy-six

one hundred and fifty-five

three

XBD23.2/45-150

forty-five

two point three two

one thousand four hundred and fifty

seventy-six

one hundred and eighty

three

XBD26.1/45-150

forty-five

two point six one

one thousand four hundred and fifty

seventy-six

one hundred and eighty

three


XBD-W type horizontal fire pump
Product Category
All product information on this website is translated by Baidu machine translation, which may not be completely accurate and is only for reference