1、 Product Overview
The PK6015 module is an intelligent electrical parameter acquisition module that can measure the true effective values of three-phase current and voltage, as well as parameters such as active power, reactive power, power factor, frequency, and electrical energy. Its output is an RS-485 digital signal, which includes parameters such as three-phase voltage, current, active power, reactive power, power factor, frequency, and electrical energy. Can replace voltage, current, power, power factor, frequency and other transmitters, as well as input modules for measuring these transmitters.
2、 Main technical parameters
Input Range - Communication 45-65Hz
Voltage range (phase voltage): 60V, 100V, 200V, 250V, 400V, 500V (or made according to user requirements)
Current range: 1A, 5A, 10A (or made according to user requirements)
Data output - true effective values of three-phase voltages Ua, Ub, Uc, three-phase currents Ia, Ib, Ic, frequency F, total active power P, total reactive power Q, total apparent power S, total power factor PF, active power Pa, Pb, Pc per phase, reactive power Qa, Qb, Qc per phase, power factors PFa, PFb, PFc per phase, apparent power Sa, Sb, Sc per phase, forward active power, reverse active power, forward reactive power, reverse reactive power
Output interface - RS-485: two-wire system, communication distance: 1200 meters, ± 15KV ESD protection
Communication Protocol - MODBUS-RTU
Baud rate -1200, 2400, 4800, 9600, 19.2K bps
Accuracy level - voltage, current 0.2 level
Active power, reactive power, power factor level 0.5
Positive and reverse active power level 0.5
Positive and negative reactive power level 1.0
Frequency level 0.2
Isolation withstand voltage -1000VDC
Power supply -+8~30VDC, power consumption<0.5W
Working temperature -20~75 ℃
Storage conditions - -20 ℃ to+80 ℃ (RH: 5% to 95% non condensing)
Instrument specifications - External dimensions: 71mm * 113mm * 59mm
Installation method: DIN rail card mounting
3、 Typical wiring diagram

4、 External dimensions
Unit: mm