The TLB-1 lightning arrester uses a hot melt explosive release device as a special matching product for the lightning arrester, which is used in series with the lightning arrester. When the lightning arrester fails, it can quickly act to remove the faulty lightning arrester from the power grid, and provide a clear disconnection sign for maintenance personnel to discover the fault point and replace the lightning arrester. On the other hand, when the lightning arrester is working normally, the disconnector does not move and exhibits low impedance, which does not affect the protection characteristics of the lightning arrester. The installation of a disconnector lightning arrester is the only way to truly achieve safe and maintenance free use, convenience and reliability. Separators are commonly used in distribution, power station, and line lightning arresters operating in developed countries and regions such as Europe, America, and Japan.
The disconnector adopts a new thermal explosion design, which has the advantages of fast response and error free operation, and can be used in conjunction with various types of lightning arresters above 3kV. The usage conditions are the same as those of lightning arresters.
The typical ampere second characteristic parameters of TLB-1 thermal explosive disconnector are as follows:
|
Current (A) |
eight hundred |
two hundred |
twenty |
five |
zero point five |
zero point zero five |
|
Action time (S) |
0.01~0.02 |
0.02~0.05 |
0.1~0.2 |
0.5~1.0 |
20~50 |
200~500 |