3021/3022/3023 Insulation resistance meter
Three testing functions:
Insulation resistance (4-scale output voltage), conductivity, AC voltage test.
The display screen simultaneously shows a bar graph and numerical insulation values.
Compare functions.
Can store 99 pieces of data.
Automatic discharge function.
The device has a live LED alarm function.
High voltage test locking function.
Battery level display and automatic shutdown function.
New material with shock-absorbing function.
The design complies with international safety standards IEC61010-1 and IEC61557.
| insulation resistance | KEW3021 | KEW3022 | KEW3023 | ||||||||||
| test voltage | 125V | 250V | 500V | 1000V | 50V | 100V | 250V | 500V | 100V | 250V | 500V | 1000V | |
| resistance range | 4.000/ 40.00/ 200MΩ |
4.000~2000MΩ | 4.000/40.00/ 200.0MΩ | four ~ 2000MΩ |
4.000/ 40.00/ 200MΩ |
4.000~2000MΩ | |||||||
| accuracy | ±(2rdg+6dgt) | ±(2rdg+6dgt) | ±(2rdg+6dgt) | ||||||||||
| Mainly effective test scope |
0.1~ 20M |
0.1~ 40M |
0.1~ 200M |
0.1~ 1000M |
0.1~ 20M |
0.1~ 20M |
0.1~ 40M |
0.1~ 200M |
0.1~ 20M |
0.1~ 40M |
0.1~ 200M |
0.1~ 1000M | |
| rated current | 1~1.2mA | ||||||||||||
| Output short-circuit current | DC below 1.5 mA | ||||||||||||
| Ω continuity | test scope | 40.00/400.0 Ω | |||||||||||
| accuracy | ±(2rdg+8dgt) | ||||||||||||
| fuse | Quick break ceramic fuse 0.5A/600V (diameter 6.35 × 32mm) | ||||||||||||
| AC voltage | test scope | AC/DC 720V | |||||||||||
| accuracy | ±(3%rdg+6dgt)(50~60Hz,AC0~600V) | ||||||||||||
| General Specifications | Other functions | Data retention, test voltage warning, power on warning LED and buzzer Automatic shutdown, remote testing, test lock (continuous testing) | |||||||||||
| Safety specifications | IEC61010-1:2001CAT.III 600V IEC61557-1,2,4 | ||||||||||||
| EMC specifications | EN61326-1 (CE marking) | ||||||||||||
| dustproof and waterproof | IP40 | ||||||||||||
| External dimensions/weight |
105 (L)×158(W)×70(D)mm | ||||||||||||
| use batteries | R6P or LR6 AA × 6 | ||||||||||||
| Attachment | 7150 (remote switch test line, flat test rod, safety crocodile clip, extension probe, wire box) 9121 shoulder strap, R6P × 6, user manual | ||||||||||||