The JDZX9-27.5 voltage transformer is a single-phase double winding and three winding epoxy resin cast fully enclosed indoor device voltage transformer, suitable for precise voltage and energy measurement and relay protection in AC systems with a rated frequency of 50Hz and a maximum working voltage of 40.5kV (nominal voltage 27.5kV).
·Environmental temperature: The normal type is+40 ℃~-15 ℃; The plateau type ranges from+25 ℃ to -15 ℃.
·Environmental humidity: The daily average relative humidity should not exceed 95%, and the monthly average should not exceed 90%; The daily average saturated vapor pressure shall not exceed 2.2 × 10-3MPa, and the monthly average shall not exceed 1.8 × 10-3MPa.
·Product type: Indoor.
·Atmospheric conditions: There is no pollution or explosive medium in the installation site that seriously affects the insulation of the transformer.
·The installation site has no severe vibrations or bumps-
·Open circuit is not allowed during product operation, otherwise there is a high voltage hazard.
·The temperature during transportation and storage ranges from+40 ℃ to -15 ℃.
·When using the product, the equipotential lead wire should be reliably connected to the high-voltage bus.
※ Technical Parameters ※
·Product execution standard: GB1207-1997 "Voltage Transformers".
·Rated insulation level: 40.5/95/200kV.
·Insulation and heat resistance grade: Grade E.
·The impulse test voltage of the transformer complies with the provisions of GB311-64, which means that the full wave is 200kV, the cut-off wave is 230kV, and the induced test voltage value is 80kV, 15s (400Hz). The secondary winding is connected to ground at 3kV for 1 minute.
|
model |
Rated voltage ratio (V) |
Accurate level or level combination |
Rated output (VA) |
Maximum output (VA) |
|
JDZX9-27.5 |
27500/√3
100/√3:100/3 |
0.2/6P |
30/100 |
six hundred |
|
0.5/6P |
90/100 |
|
1/6P |
180/100 |
|
27500/√3
100/√3:100/√3:100/3 |
0.2/0.5/6P |
20/30/100 |
three hundred |
JDZX9-27.5 Voltage Transformer