1、 Characteristics
19 signal compatible inputs, range and decimal point can be set arbitrarily
Four relay alarm outputs: upper limit, upper limit, lower limit, and lower limit
PV window displays measurement values, SV window displays alarm values
Specially suitable for automatic control systems with multiple points and different output segments
2、 Technical parameters
1. Working power supply: AC/DC85-260V (other voltages can be customized)
2. Power consumption: less than 5W
3. Input signals: (19 types in total)
Thermocouples: T, R, J, WRe3-25, B, S, K, E
Thermistor: Pt100, Cu50
Standard signal: 0-375 Ω, 0-75mV, 0-30mV
0~5V、1~5V、0~10V、0~10mA
0~20mA、4~20mA
4. Display range: -1999 to 9999
5. Cold end compensation: 0-50 ℃
6. Basic error: 0.2% FS ± 1 word
7. Feed output: DC24V/30mA
8. Contact capacity: AC250V/3A; DC24V/5A
9. Transmission output signal: 0-20mA, 4-20mA
10. Transmission load capacity: not less than 500 Ω
11. Operating environment: 0-50 ℃; ≤85%RH
3、 Model Description