XMJ intelligent traffic integrator
I. Overview
The XMJ flow integrator receives pulse signals and analog standard signals, and is compatible with various forms of flow sensors and transmitters. It can measure the volume flow rate and mass flow rate of general liquids. This flow integrator is widely used in industries such as sewage treatment, municipal, steel, chemical, thermal, and metallurgical.
2、 Characteristics
Accumulated values and parameter settings will not be lost after power failure and can be saved for 10 years
Equipped with signal square root function, it can directly input differential pressure transmitter signals
Wide range switch power supply, multiple protections, safe and efficient
Free input of current, voltage, and pulse, with arbitrary range setting
Small signal cutoff and filtering function, effectively eliminating jitter and interference
3、 Technical parameters of XMJ intelligent flow integrator
1. Power supply voltage: AC/DC85-260V
2. Analog inputs: 0-5V, 1-5V, 4-20mA
3. Pulse input: rectangular wave, sine wave, triangular wave 0-10KHz; Amplitude ≥ 4V
4. Display range: Instantaneous flow rate: 0-9999
Accumulated value range: 0~9999999.999
5. Measurement and control cycle: 0.3 seconds
6. Basic error: 0.2% FS ± 1 word
7. Instantaneous alarm: Two alarm outputs for upper and lower limits
8. Cumulative alarms: upper limit alarm on one channel
9. Small signal resection: 0-25.0%
10. Feed output: DC24V/30mA; DC12V/30mA dual output
11. Contact capacity: AC250V/3A
12. Transmission output: Instantaneous flow transmission output
13. Communication output: RS485 (optoelectronic isolation) modbus_STU protocol
14. Dimensions: 160 × 80 × 124mm
15. Hole size: 152 × 76mm
16. Operating environment: 0-50 ℃; <85%RH
3、 Model Description