| Product name: | UPS) series inverter power supply | ||||||
| specification: | ![]() |
||||||
| Category: | transformer equipment -- inverter | ||||||
| Price: | factory price | ||||||
| Brand: | Shanghai | ||||||
| Place of Origin: | China | ||||||
| Available Quantity: | batch | ||||||
| delivery cycle: | Spot goods (or inquire by telephone) | ||||||
|
|||||||
Technical parameters:
The MT/MTT series UPS is a truly online uninterruptible power supply with pure sine wave output. This series of machines adopts the latest power module, making UPS more efficient and reliable. The SPWM full bridge inverter and isolation transformer output uninterruptible power supply have super strong load impact and overload capabilities. Suitable for: computer and network systems, military communication systems, satellite communication systems, advanced medical equipment, precision instrument equipment, monitoring and security systems, fire lighting systems, financial securities networks, radio transmission and reception systems, information transmission systems, and other fields. Through its intelligent remote control and telemetry interface, it can also provide intelligent management of UPS remote monitoring.
|
Model number Model |
Single entry Single out |
MT 1KVA |
MT 2KVA |
MT 3KVA |
MT 5KVA |
MT 6KVA |
MT 10KVA |
MT 15KVA |
MT 20KVA |
MT 30KVA |
MT 40KVA | |
|
Three in single out |
MTT 5KVA |
MTT 6KVA |
MTT 10KVA |
MTT 15KVA |
MTT 20KVA |
MTT 30KVA |
MTT 40KVA | |||||
|
Rated capacity Rated capacity |
800W |
1600W |
2400W |
4000W |
4800W |
8000W |
12000W |
16000W |
24000W |
32000W | ||
|
communication input AC input |
Number of phases Phase NO. |
Single in&Single out |
single-phase (L+N+G) | |||||||||
|
Three in single out Tree in&Single out |
Three-phase (3W+N+G) | |||||||||||
|
Voltage Voltage |
Single in&Single out |
220VAC±25% | ||||||||||
|
Three in single out Tree in&Single out |
380VAC±25% | |||||||||||
|
Frequency range |
50/60±5%Hz | |||||||||||
|
communication output Ac output |
Voltage Voltage |
220±10% | ||||||||||
|
Voltage Accuracy |
±1% | |||||||||||
|
Frequency |
50Hz/60Hz frequency accuracy ± 0.5% (synchronized with mains power supply) | |||||||||||
|
Waveform |
Sine wave, THD<3% (linear load) Sine wave, THD<3% (linear load) | |||||||||||
|
power factor Power factor |
0.8 lag 0.8 lag | |||||||||||
|
Peak current coefficient |
3:1, suitable for rectifying loads 3:1, suitable for rectifying load | |||||||||||
|
Dynamic voltage Transient range |
0-100% load change, ± 4%<10% 0-100% load change,<10% ± 4 | |||||||||||
|
switch time Transfer time |
0 | |||||||||||
|
static switch time (ms) |
0 | |||||||||||
|
battery battery |
type Type |
Sealed maintenance free lead-acid battery (Machine not included) Including batteries) | ||||||||||
|
spare time back-up time |
Standard 5 minutes, | |||||||||||
|
Charging time Charge time |
Within 7-12 hours Charging 90% up to 90% after charge for 7-16 hours |
10-24 hours Internal charging 90% | ||||||||||
|
Quantity (12V, only) |
four |
eight |
ten |
sixteen |
thirty |
thirty-two | ||||||
|
DC voltage |
48V |
96V |
120V |
192V |
192V |
192V |
192V |
192V |
360V |
384V | ||
|
Efficiency Efficiency |
>80% |
>83% |
>86% | |||||||||
|
Noise (at a distance of one meter) |
<50dB |
<55dB |
<60dB | |||||||||
|
Protection |
Switching to bypass power supply when overloaded, overload/short circuit protection, surge voltage protection (220VUPS-470V), noise suppression capability up to FCCA level | |||||||||||
|
Display display |
LED indicator light |
Mains input/bypass/inverter/battery/overload/fault Supply input/bypass/inversision/battery/overload/fault | ||||||||||
|
LED LCD (Liquid Crystal Display) |
Manufacturer/Input Voltage/Output Voltage/Battery Voltage/Frequency/Load Percentage/UPS Status | |||||||||||
|
Alarm Warm |
Mains power failure |
Pulsed sound every 4 seconds | ||||||||||
|
Low battery voltage |
Pulsed sound per second | |||||||||||
|
Overload Overload |
Continuous alarm sound Successful alarm | |||||||||||
|
UPS malfunction |
Continuous alarm sound Successful alarm | |||||||||||
|
Computer monitoring interface Intelligent RS232 interface |
Input/output voltage, battery capacity, load power, mains frequency, timed shutdown, internal temperature, timed shutdown, etc | |||||||||||
|
Usage environment Using environment |
Temperature Temperature |
0℃-40℃ | ||||||||||
|
relative humidity |
30% -90% frost free 30% -90% no conditioning | |||||||||||
|
altitude |
<1000 meters (1% power reduction for every 100 meters increase, maximum 4000 meters)<1000 meters (the power will drop 1% per increase of 100m,max.∶4000m) | |||||||||||
|
Weight (kg) Weight (kg) |
Single in, single out |
thirty-eight |
fifty-seven |
sixty-nine |
eighty-three |
eighty-eight |
one hundred and thirty-six |
one hundred and sixty-two |
two hundred and forty-five |
two hundred and eighty-seven |
three hundred and forty-two | |
|
Three in single out |
ninety-three |
one hundred and thirteen |
one hundred and eighty-six |
two hundred and thirty-five |
two hundred and seventy-seven |
three hundred and thirty-two |
three hundred and ninety-eight | |||||
|
Overall dimensions (mm) |
Long (L) |
five hundred and sixty-five |
five hundred and fifty-five |
six hundred and thirty-five |
five hundred and fifty |
seven hundred and ninety | ||||||
|
Width (W) |
two hundred and eighty |
two hundred and sixty-five |
two hundred and seventy |
four hundred and fifty |
five hundred and eighty | |||||||
|
High (H) |
three hundred and fifty-five |
five hundred and seventy |
six hundred and ninety |
one thousand |
one thousand one hundred and eighty | |||||||