1. Application
WRCK and WRPK armored thermocouples are usually used in conjunction with display instruments, recording instruments, electronic computers, and other devices. Directly measure the surface temperature of liquids, vapors, gases, and solids within the range of 0 ° C to 1300 ° C in various production processes.
2. Characteristics
·Less thermal response time, reducing dynamic errors;
·Flexible installation and use;
·Large measurement range;
·High mechanical strength and good pressure resistance;
3. Working principle of WRCK and WRPK armored thermocouple
The electrodes of armored thermocouples are composed of two different conductor materials. When there is a temperature difference between the measuring end and the reference end, a thermoelectric potential is generated, and the working instrument displays the temperature value corresponding to the thermoelectric potential.
4. Main technical parameters
Product execution standards
IEC584
IEC1515
GB/T16839-1997
JB/T5582-91
5. WRCK, WRPK armored thermocouple measurement range and tolerance
| model |
graduation mark |
Tolerance level |
| I |
II |
| Tolerance value |
Temperature measurement range ° C |
Tolerance value |
Temperature measurement range ° C |
| WRNK |
K |
±1.5°C |
-40~+375 |
±2.5 °C |
-40~+333 |
| ±0.004ltl |
375~1000 |
±0.0075 ltl |
333~1200 |
| WRMK |
N |
±1.5°C |
-40~+375 |
±2.5°C |
-40~+333 |
| ±0.004 ltl |
375~1000 |
±0.0075 ltl |
333~1200 |
| WREK |
E |
±1.5°C |
-40~+375 |
±1.5°C |
-40~+333 |
| ±0.004 ltl |
375~800 |
±0.004 ltl |
333~900 |
| WRFK |
J |
±1.5°C |
-40~+375 |
±1.5°C |
-40~+333 |
| ±0.004 ltl |
375~750 |
±0.004 ltl |
333~750 |
| WRCK |
T |
±1.5°C |
-40~+125 |
±1°C |
-40~+133 |
| ±0.004 ltl |
125~350 |
±0.0075 ltl |
133~1000 |
| WRPK |
S |
±1°C |
0~+1100 |
±2.5°C |
0~600 |
| ±[0.003(t-1100)] |
1100~1600 |
±0.0025 ltl |
600~1600 |
6. Room temperature insulation resistance
The insulation resistance between the electrode and the outer sheath of the armored couple is greater than 1000M Ω when the ambient temperature is 20 ± 15 ° C and the relative humidity is not greater than 80%. The test voltage is 500 ± 50V (DC).
The insulation resistance of a 1m long sample is 1000M Ω;
The insulation resistance of a 10m long sample is 100 M Ω;
7. Wire diameter and material
| Even silk form |
Single branch type |
Double branch type |
| Diameter of casing |
Ф2 Ф3 Ф4 Ф5 Ф6 Ф8 |
Ф3 Ф4 Ф5 Ф6 Ф8 |
| Material of casing |
E﹑J﹑T |
1Cr18Ni9Ti |
1Cr18Ni9Ti |
| K﹑N |
1Cr18Ni9Ti GH3030 |
1Cr18Ni9Ti GH3030 |
| S |
GH3039 |
GH3039 |
Model and specifications: