Characteristics of SLK60 capacitor level switch
Adopting advanced data storage technology, parameters are not lost after power failure, and data can be saved for up to 10 years.
This product adopts internationally advanced RF capacitance measurement and microcontroller technology, which can detect liquids such as water, wastewater, or mud, especially strong corrosive media; The measurement temperature can reach 180 ℃, and the pressure resistance can reach 4MPa.
Easy to operate, just press the setting button to complete the alarm point setting. The setting key also has the feature of anti vibration to avoid unnecessary modification of the alarm point.
The upper limit alarm mode and lower limit alarm mode can be flexibly set. The control method is flexible, and users can choose between normally open or normally closed contacts.
It can overcome the influence of adhesive layer and material splashing on the measurement of the probe. In these situations, capacitor switches will not cause misoperation.
Using polytetrafluoroethylene to protect the probe, the detection area has no movable parts, is resistant to impact, high temperature, high pressure, corrosion, and is not easy to adhere.
Technical parameters of SLK60 capacitor level switch
Environmental temperature: -30~70 ℃;
Environmental humidity: ≤ 95% RH;
Protection level: IP65;
Power supply: 220VAC ± 10% or 24VDC ± 15%;
Relay contact capacity: 250VAC/3A or 24VDC/5A;
Relative dielectric constant: ε ≥ 1.6;
Delay time: 0, 2, 4, 8, 16, 32 seconds;
Power consumption: ≤ 1W;
Electrical interface: M20 × 1.5;
Probe length: 350mm or specified by the user;
Process temperature: ordinary -20~80 ℃; High temperature -25~180 ℃;
Process pressure: -0.1 to 4.0 MPa;
Installation Diagram


SLK60 capacitor level switch