The JCZR5 series AC high-voltage vacuum contactor fuse combination device has a rated voltage of 12KV/7.2KV and is an indoor device in a three-phase AC 50Hz distribution system. It can be used to control and protect high-voltage motors of 1200kW and below and transformers of 1600kVA and below in power plants, mines, metallurgy, chemical industries, and other industries. This product has a reasonable structure, high reliability, long electrical life, low maintenance, small size, light weight, and extremely long mechanical life. It is a high-performance, non maintenance combination electrical appliance that can completely replace imported products.
Rated parameters:
| name |
Numerical value |
| JCZ5-12/D400-4 |
JCZR5-12/D160-50 |
| rated voltage |
12kV |
| Rated insulation level |
1-minute power frequency withstand voltage |
Alternating and relative to each other |
42kV |
| fracture |
42kV |
| Operating mechanism and auxiliary circuit |
2.0kV |
| Lightning impulse withstand voltage (peak) phase to phase and relative to ground |
75kV |
| rated frequency |
50Hz |
| rated current |
400A |
160A |
| Maximum rated breaking current (25 times) |
3200A |
|
| Minimum rated breaking current (25 times) |
80A |
| Maximum breaking current (3 times) |
4.0kA |
| Rated short-time withstand current |
4.0kA |
| Rated short-time withstand current duration |
4S |
| Rated short-circuit breaking current (expected value) |
— |
50(40)kA |
| Rated closing current (100 times) |
4kA |
— |
| Rated short-circuit closing current |
10kA |
100 (expected value) kA |
| Handover current |
— |
3150A |
| Half current allowed current |
50(40)kA |
— |
| main circuit resistance |
≤150μΩ |
≤250μΩ |
| electrical life |
AC—3 |
25 × 104 times |
| AC—4 |
10 × 104 times |
| mechanical life |
Electricity maintenance |
3.0 × 105 times |
| Mechanical Maintenance |
3.0 × 105 times |
| Number of operating cycles per hour |
Electricity maintenance |
300 (1800) times |
| Mechanical Maintenance |
300 times |
| Rated closing operation voltage/current |
AC:220/3、110/6 V/A |
| DC:220/3、110/6 V/A |
| Close and maintain voltage/current |
AC:220/0.16、110/0.32 V/A |
| DC:220/0.16、110/0.32 V/A |
| Rated opening operation voltage/current (only for mechanical maintenance) |
AC:220/1.3、110/2.5 V/A |
| DC:220/1.3、110/2.5 V/A |
| auxiliary switch |
Connection points |
Normally Open |
3 (4) pieces |
| normally closed |
3 of them |
| Rated working current |
AC |
4A |
| DC |
0.4A |
Mechanical characteristic parameters:
| Interphase center distance |
150±1.5mm |
| contact gap |
6mm |
| overstroke |
1.5±0.5mm |
| Allowable wear thickness for dynamic and static contacts |
3mm |
| Average closing speed |
0.2±0.1m/s |
| Average opening speed |
Electricity maintenance |
0.45±0.15m/s |
| Mechanical Maintenance |
0.45±0.15m/s |
| Synchronization of three-phase contact closing and opening |
≤2ms |
| Contact closing bounce time |
≤5ms |
| Closing time |
≤150ms |
| Opening time |
≤50ms |
| Note: The average closing and opening speeds refer to the average speed within the opening distance of the moving and stationary contacts, and only measure the speed value of phase B. |
JCZR5-12/D160-50 AC High Voltage Vacuum Contactor Fuse Combination Electrical Appliance Outline Drawing:

JCZR5-12/D160-50 AC High Voltage Vacuum Contactor Fuse Combination Electrical Appliance