| Product name: | Indoor AC high voltage vacuum load switch | ||||||
| specification: | ![]() |
||||||
| Category: | High voltage electrical appliances -- Indoor high-voltage load switch | ||||||
| Price: | factory price | ||||||
| Brand: | Shanghai | ||||||
| Place of Origin: | China | ||||||
| Available Quantity: | batch | ||||||
| delivery cycle: | Spot goods (or inquire by telephone) | ||||||
|
|||||||
|
serial number |
project |
unit |
load switch |
combined electrical apparatus |
grounding switch |
|
one |
rated voltage |
KV |
forty point five |
forty point five |
forty point five |
|
two |
rated current |
A |
1250 630 |
sixty-three |
-- |
|
three |
rated frequency |
HZ |
fifty |
fifty |
fifty |
|
four |
Rated short-circuit breaking current |
KA |
-- |
thirty-one point five |
-- |
|
five |
Rated line charging interruption current |
A |
two point one |
two point one |
-- |
|
six |
Rated ground fault breaking current |
A |
sixty-three |
sixty-three |
-- |
|
seven |
Rated short-circuit closing current |
KA |
fifty |
-- |
-- |
|
eight |
Rated peak withstand current |
KA |
fifty |
-- |
fifty |
|
nine |
Rated short-time withstand current/duration |
KA |
20/4 |
-- |
20/2 |
|
ten |
Rated breaking transfer (handover) current |
A |
-- |
one thousand and seven hundred |
-- |
|
eleven |
Rated Active load breaking current |
A |
1250 630 |
-- |
-- |
|
twelve |
Rated closed-loop breaking current |
A |
1250 630 |
-- |
-- |
|
thirteen |
Rated cable charging current |
A |
twenty-one |
twenty-one |
-- |
|
fourteen |
Rated voltage for secondary circuit operation |
V |
AC/DC220、110 |
||
|
fifteen |
1-minute power frequency withstand voltage (effective value) to ground, phase to phase, vacuum break/isolation break |
KV |
95/118 | ||
|
sixteen |
Full wave lightning impulse withstand voltage (peak) to ground, phase to phase, vacuum break/isolation break |
KV |
185/215 | ||
|
seventeen |
main circuit resistance |
μΩ |
≤ 120 (except for fuses) | ||
|
eighteen |
mechanical life |
time |
five thousand |
two thousand |
two thousand |
|
nineteen |
Maximum/minimum energy storage and closing operation voltage |
V |
AC 242/187 |
||
|
twenty |
Maximum/minimum voltage for opening operation |
AC 264/143 |
|||
|
twenty-one |
Switch level |
M2/E2 |
M1 |
M1/E0 | |
5.2 Mechanical performance parameters (see: Table 2) (Table 2)
|
serial number |
project |
unit |
Vacuum arc extinguishing chamber |
Isolation knife switch |
grounding knife switch |
|
one |
contact gap |
mm |
17±1 |
≥350 |
-- |
|
two |
Contact overtravel |
mm |
4±1 |
-- |
-- |
|
three |
Average opening speed |
M/s |
1.6±0.2 |
-- |
-- |
|
four |
Average closing speed |
M/s |
0.8±0.2 |
-- |
-- |
|
five |
Three pole opening and closing are not synchronized |
ms |
≤2 |
≤3mm |
-- |
|
six |
Rated closing bounce time |
ms |
≤2 |
-- |
-- |
|
seven |
Center distance between poles |
mm |
410+2 |
410+2 |
410+2 |
|
Opening and closing operation force |
N |
two hundred | |||
5.3 Electric parameters of spring operated mechanism. See: Tables 3 and 4
Magnetic single-phase DC energy storage motor (Table 3)
|
model |
rated voltage |
Rated output power |
Normal operating voltage range |
|
ZYJ220-53 |
AC/DC220V |
≤70W |
85% -110% rated voltage |
Opening electromagnet (independent power supply) (Table 4)
|
Rated working voltage (V) |
AC220 |
AC110 |
DC220 |
|
Rated working current (A) |
two point six seven |
two point nine three |
two |
|
Rated electrical power (W) |
< 587 |
< 312 |
four hundred and forty |
|
Coil resistance value at 20 ℃ (Ω) |
30±3 |
18±1.7 |
58±10 |
|
Normal operating voltage range |
65% -120% rated working voltage reliable tripping; Do not disconnect when the rated operating voltage is less than 30% | ||
6.1 Basic Structure
6.1.1 This combination electrical device is a three pole linkage structure. It mainly consists of a frame, a vacuum arc extinguishing chamber, an isolation knife switch, a fuse, a grounding knife switch, a trip transmission device, and a spring operating mechanism. The isolation knife switch and vacuum arc extinguishing chamber are fixed to the frame through insulators, and the fuse is installed on the back of the isolation knife switch. The grounding knife switch spindle is directly installed at the lower part of the frame. The spring operating mechanism is installed on the left side panel of the frame, and the operation mode is side operation. The operating mechanism drives the switch spindle, which rotates and uses a crank arm to drive the vacuum arc extinguishing chamber or isolation knife switch through an insulated operating rod, achieving the operation of opening and closing. The grounding knife switch and the isolation knife switch are connected together through a transmission link, and the two are interlocked during operation.