Indoor AC high voltage vacuum load switchDetailed product description:Column tabs
FZN-40.5D/T630-20 indoor AC high-voltage vacuum load switch and FZRN-40.5D/T630-31.5 indoor AC high-voltage vacuum load switch fuse combination (hereinafter referred to as: vacuum load switch) are designed specifically for 35KV box type substations and can also be used as independent electrical units in power systems (cabinet installation or wall installation).
This product has a small size, easy installation, and simple operation. Its structure is scientifically reasonable, its movements are flexible and reliable, and it has obvious isolation fractures. The load switch can achieve maintenance free operation, and the combination electrical appliance can be equipped with a series of pin type fuses, which are safe and convenient to replace.
2. Purpose
The FZN-40.5 series vacuum load switch is used in AC 50HZ networks with a rated voltage of 40.5KV, as a means of breaking load current, overload current, and short-circuit current. The operation mode has both manual and electric functions, especially suitable for places that require oil-free, maintenance free, and frequent operation.

3. Model Description
Model name
FZN-40.5/T630-20 Indoor AC High Voltage Vacuum Load Switch (630A; 1250A)
FZN-40.5D/T630-20 Indoor AC High Voltage Vacuum Load Switch with Grounding Switch (630A; 1250A)
FZRN-40.5/T630-31.5 Indoor AC High Voltage Vacuum Load Switch Fuse Combination Apparatus (6.3A-125A)
FZRN-40.5D/T630-31.5 Indoor AC High Voltage Vacuum Load Switch Fuse Combination with Grounding Switch (6.3A-125A)

Note: The insulator of the vacuum load switch can be equipped with a sensor with a live display.
4. Operating environment
A. Altitude not exceeding 1000m; 2000m; 3000m; 3500m (The user must specify the requirements when placing an order, and if not specified, the altitude is 1000m)
B. The ambient air temperature ranges from -25 ℃ to+40 ℃;
C. Relative humidity: daily average not exceeding 95%, monthly average not exceeding 90%; Water vapor pressure: daily average not exceeding 2.2kPa; The monthly average value does not exceed 1.8kPa;
D. The surrounding air is not significantly polluted by dust, smoke, corrosive or flammable gases, water vapor, or salt spray;
E. The amplitude of electromagnetic interference induced in the secondary system shall not exceed 1.6KV;

5. Main technical parameters of FZN, FZRN-40.5D/T630 indoor AC high-voltage vacuum load switch
5.1 Electrical Performance Parameter Table (see: Table 1) (Table 1)

serial number

project

unit

load switch

combined electrical apparatus

grounding switch

one

rated voltage

KV

forty point five

forty point five

forty point five

two

rated current

A

1250 630

sixty-three

--

three

rated frequency

HZ

fifty

fifty

fifty

four

Rated short-circuit breaking current

KA

--

thirty-one point five

--

five

Rated line charging interruption current

A

two point one

two point one

--

six

Rated ground fault breaking current

A

sixty-three

sixty-three

--

seven

Rated short-circuit closing current

KA

fifty

--

--

eight

Rated peak withstand current

KA

fifty

--

fifty

nine

Rated short-time withstand current/duration

KA

20/4

--

20/2

ten

Rated breaking transfer (handover) current

A

--

one thousand and seven hundred

--

eleven

Rated Active load breaking current

A

1250 630

--

--

twelve

Rated closed-loop breaking current

A

1250 630

--

--

thirteen

Rated cable charging current

A

twenty-one

twenty-one

--

fourteen

Rated voltage for secondary circuit operation

V

AC/DC220、110

fifteen

1-minute power frequency withstand voltage (effective value) to ground, phase to phase, vacuum break/isolation break

KV

95/118

sixteen

Full wave lightning impulse withstand voltage (peak) to ground, phase to phase, vacuum break/isolation break

KV

185/215

seventeen

main circuit resistance

μΩ

≤ 120 (except for fuses)

eighteen

mechanical life

time

five thousand

two thousand

two thousand

nineteen

Maximum/minimum energy storage and closing operation voltage

V

AC 242/187

twenty

Maximum/minimum voltage for opening operation

AC 264/143

twenty-one

Switch level

M2/E2

M1

M1/E0


5.2 Mechanical performance parameters (see: Table 2) (Table 2)

serial number

project

unit

Vacuum arc extinguishing chamber

Isolation knife switch

grounding knife switch

one

contact gap

mm

17±1

≥350

--

two

Contact overtravel

mm

4±1

--

--

three

Average opening speed

M/s

1.6±0.2

--

--

four

Average closing speed

M/s

0.8±0.2

--

--

five

Three pole opening and closing are not synchronized

ms

≤2

≤3mm

--

six

Rated closing bounce time

ms

≤2

--

--

seven

Center distance between poles

mm

410+2

410+2

410+2

Opening and closing operation force

N

two hundred


5.3 Electric parameters of spring operated mechanism. See: Tables 3 and 4

Magnetic single-phase DC energy storage motor (Table 3)

model

rated voltage

Rated output power

Normal operating voltage range

ZYJ220-53

AC/DC220V

≤70W

85% -110% rated voltage


Opening electromagnet (independent power supply) (Table 4)

Rated working voltage (V)

AC220

AC110

DC220

Rated working current (A)

two point six seven

two point nine three

two

Rated electrical power (W)

< 587

< 312

four hundred and forty

Coil resistance value at 20 ℃ (Ω)

30±3

18±1.7

58±10

Normal operating voltage range

65% -120% rated working voltage reliable tripping; Do not disconnect when the rated operating voltage is less than 30%

6.1 Basic Structure

6.1.1 This combination electrical device is a three pole linkage structure. It mainly consists of a frame, a vacuum arc extinguishing chamber, an isolation knife switch, a fuse, a grounding knife switch, a trip transmission device, and a spring operating mechanism. The isolation knife switch and vacuum arc extinguishing chamber are fixed to the frame through insulators, and the fuse is installed on the back of the isolation knife switch. The grounding knife switch spindle is directly installed at the lower part of the frame. The spring operating mechanism is installed on the left side panel of the frame, and the operation mode is side operation. The operating mechanism drives the switch spindle, which rotates and uses a crank arm to drive the vacuum arc extinguishing chamber or isolation knife switch through an insulated operating rod, achieving the operation of opening and closing. The grounding knife switch and the isolation knife switch are connected together through a transmission link, and the two are interlocked during operation.

FZN, FZRN-40.5D/T630 Indoor AC High Voltage Vacuum Load Switch Dimensions

Indoor AC high voltage vacuum load switch