The FN16A-12RD/200-31.5 combination electrical appliance is suitable for networks with AC 50Hz and rated voltage of 6-10KV. FN16A-12D/630 can disconnect load current, FN16A-12RD/200-31.5 can disconnect load current, overload current and short-circuit current, especially suitable for places without oil, without maintenance and frequent operation requirements. This product can be equipped with a CS6-I type operating mechanism, and can also be operated directly on the switch without the need for an additional operating mechanism. The FN16A-12D/12-J switch can achieve both electric and manual operation simultaneously.
Environmental conditions for use
A 、 Surrounding air temperature: upper limit+40oC;
Lower limit -25 oC
b 、 Relative humidity: monthly average not exceeding 90%;
Daily average not exceeding 95%
c 、 Altitude not exceeding: 1000m;
d 、 There is no obvious pollution such as corrosion or flammable gases around;
e 、 No frequent severe vibrations.
FN16A-12RD/200-31.5 Vacuum Load Switch Combination Electrical Appliance Model Meaning
| serial number |
project |
unit |
parameter |
| one |
Rated voltage and maximum operating voltage |
KV |
twelve |
| two |
rated frequency |
Hz |
fifty |
| three |
Maximum rated current of fuse |
A |
two hundred |
| four |
Rated transfer current |
A |
three thousand one hundred and fifty |
| five |
The opening time of the fuse triggered switch |
ms |
thirty-one0+5 |
| six |
Rated short-circuit breaking current (expected effective value) |
KA |
thirty-one point five |
| seven |
Rated short-circuit breaking and closing current (expected peak) |
KA |
eighty |
| eight |
1-minute power frequency withstand voltage (effective value) to ground, phase to phase, vacuum break/isolation break |
KV |
42/48 |
| nine |
Lightning impulse withstand voltage (peak) to ground, phase to phase, vacuum break/isolation break |
KV |
75/85 |
| ten |
Fuse impact output energy |
J |
2-5 |

FN16A-12RD/200-31.5 Vacuum Load Switch Combination Electrical Appliance