Product Description
PRG-2000 detection end/operation end isolated safety barrier, channel one transmits standard 4mA~20mA current signal from the safety side to the danger side, driving the on-site actuator to work. Channel 2 provides a 24V isolated DC power supply from the safe area to the hazardous area for a two-wire transmitter. The transmitter generates a 4mA to 20mA current signal that is isolated from the hazardous area and transmitted to the safe side output (or converted to a 1V to 5VDC output). This product requires independent power supply (fully isolated between power supply, input, and output)
Main technical specifications
Power supply voltage: 20V-35Vdc power supply
Number of channels: Two independent channels
Power consumption: about 2W (24V power supply, 20mA output)
Input signal range: 4mA~20mADC
Output signal range: 4mA~20mADC
Allowable output load capacity: 0-650 Ω
performance metrics
Insulation strength: 2500Vac/min between intrinsic safety end and non intrinsic safety end, 1000Vac/min between non intrinsic safety end and non intrinsic safety end
Output accuracy: Channel 1: 0.1% F.S
Channel 2:0.1% F.S
Temperature drift: 0.01% F.S/℃
Working temperature: -20 ℃~+60 ℃
Relative temperature: 35% to 85% RH
Storage temperature: -40 ℃ to+80 ℃
Structure and external dimensions
Product structure: 35mm rail card, ABS shell material, plug-in terminal
Dimensions: 22.5 × 114.5 × 99 (mm)
Whole machine weight: 150g
Product Features
Channel 1: connected to valve positioner and electric/gas converter, Channel 2: connected to two-wire transmitter, in compliance with EMC standards
installation site
The surrounding air should be free of corrosive media that can corrode chromium, nickel, and silver coatings. It is suitable for use in Zone 0, Zone 1, Zone 2 of the site and equipment, as well as hazardous areas IIA, IIB, and IIC,
Channel 1: Valve positioner, electric/pneumatic converter
Channel 2: Two wire transmitter
Safety and Explosion proof Certification Parameters
National Quality Supervision and Inspection Center for Explosion proof Electrical Products (CQST)
Explosion proof mark: [EXia] (IIC)
Authentication parameters: terminals (between 9.10.11 and 13.14)
Um = 250V Uo = 28V Io = 93mA
Po = 0.65W Lo = 2.4mH Co = 0.05uF
PRG-2000 Isolation Safety Barrier Wiring Diagram for Detection and Operation Terminals

Outline dimension drawing (mm)