PRG-1600/161/1620 switch input relay output isolation safety barrier description
The switch input isolation safety barrier accepts contact/proximity switch inputs from the hazardous area side, and transmits them to the safe area output through the safety barrier isolation. It has the function of relay output normally open/normally closed conversion setting.
PRG-1600/161/1620 switch input relay output isolation safety barrier main technical specifications
Working power supply: 20V-35Vdc
Power consumption: approximately 1.0W
On site sensor side power supply voltage: about 8V (open circuit)
Signal input characteristics:
When the on-site input current is greater than 2.1mA, it means "ON"
When the on-site input current is less than 1.2mA, it means "OFF"
Switching hysteresis effect: 200us
Relay output characteristics:
Response time: 20ms
Drive capability: 250Vac/2A, 30Vdc/2A
Output function mode:
Micro toggle switch 1 and 2 settings (control channels 1 and 2 respectively)
On the "ON" side, the relay outputs "normally closed"
Set the "OFF" side, the relay output is "normally open"
Alarm function: (K3 is set to the "ON" side, 5 and 6 are the alarm terminals)
On site input current>7mA, short circuit alarm (SC)
On site input current<0.1mA, open circuit alarm (LB)
Alarm relay output characteristics:
Response time: 20ms
Drive capability: 250Vac/2A, 30Vdc/2A
Load type: resistive load
performance metrics
Insulation strength: 2500Vac/min between intrinsic safety end and non intrinsic safety end, 1000Vac/min between non intrinsic safety end and non intrinsic safety end
Working temperature: -20 ℃~+60 ℃
Relative humidity: 35% to 85% RH
Storage temperature: -40 ℃ to+80 ℃
Structure and external dimensions
Product structure: 35mm rail mounted card type
ABS shell material
Plug in terminal
Dimensions: 22.5 × 114.5 × 99 (mm)
Whole machine weight: 150g
Product Features
Wide range power supply, selectable output mode, compliant with EMC standards
installation site
The surrounding air should not contain any medium that corrodes chromium, nickel, and silver coatings
Applicable on-site and equipment
Zone 0, Zone 1, Zone 2, Zone IIA, Zone IIB, Zone IIC hazardous areas, in compliance with DIN19234 and NAMUR proximity switches, switches and other on-site equipment
Safety and Explosion proof Certification Parameters
National Quality Supervision and Inspection Center for Explosion proof Electrical Products (CQST)
Explosion proof mark: [EXia] (IIC)
Authentication parameters: Terminal (between 9.10 and 11.12)
Um = 250V Uo = 10.5V Io = 14mA
Po = 0.037W Lo = 165mH Co = 2.4uF
PRG-1600/161/1620 switch input relay output isolation safety barrier wiring diagram

Outline dimension drawing (mm)