HomeYour location:Homeinstrumentation and metersElectrical instrumentssignal isolator → PRG-1802 Frequency isolated safety barrier
Column tabs 
Product name: PRG-1802 Frequency isolated safety barrier
specification: PRG-1802 Frequency isolated safety barrier
  Zoom Zoom in on the image
Category: instrumentation and meters -- signal isolator
Column tabs 
Price: factory price
Brand: Shanghai
Place of Origin: China
Column tabs 
Available Quantity: batch
delivery cycle: Spot goods (or inquire by telephone)
tabs
  Shanghai Beiyuan Industry and Trade Co.,Ltd
+86-21-66770508
+86-13901609058

Email 91way@163.com
Wechat 13901609058(Wechat)


PRG-1802 Frequency isolated safety barrierDetailed product description:Column tabs

Product Description
The PRG-1802 frequency isolated safety barrier enables the safe transmission of frequency signals generated by hazardous area instruments to the safe area output. The input uses a hysteresis comparison circuit with high anti-interference performance, while providing power to on-site instruments. This product requires independent power supply, with power supply, input, and output isolated.

Main technical specifications
Power supply voltage: 20V-35Vdc power supply
Number of channels: single channel
Power consumption: approximately 2.5W (20mA)
Input signal:
Maximum distribution voltage for instruments in hazardous areas: 26V
Minimum distribution voltage: 16V (output 20mA)
Signal level: High level ≥ 4V, low level ≤ 1V
Frequency ≤ 10kHz, amplitude ≤ 24V, duty cycle ≥ 20%
Output signal:
Signal level: Low level ≤ 0.5V
High level ≥ 4.5V
Drive current i: ≤ 15mA
Load resistance: ≥ 2K Ω
performance metrics
Insulation strength: 2500Vac/min between intrinsic safety end and non intrinsic safety end, 1000Vac/min between non intrinsic safety end and non intrinsic safety end
Output accuracy: 0.1% F.S
Temperature drift: 0.01% F.S/℃
Working temperature: -20 ℃~+60 ℃
Relative temperature: 35% to 85% RH
Storage temperature: -40 ℃ to+80 ℃

Structure and external dimensions
Product structure: 35mm guide rail card mounting,
ABS shell material,
Plug in terminal
Dimensions: 22.5 × 114.5 × 99 (mm)
Whole machine weight: 150g

Product Features
IIC explosion-proof grade, in compliance with EMC standards
installation site
The surrounding air should not contain any medium that corrodes chromium, nickel, and silver coatings
Applicable on-site and equipment
Installed in a safe location, it can be used with 0-zone frequency devices containing hazardous gases such as IIA, IIB, and IIC.
Safety and Explosion proof Certification Parameters
National Quality Supervision and Inspection Center for Explosion proof Electrical Products (CQST)
Explosion proof mark: [EXia] (IIC)
Authentication parameters: Terminal (9-10)
Um = 250V Uo = 28V Io = 93mA
Co = 0.083uF Lo = 4.2mH Po = 0.66W
Authentication parameters: Terminal (11-12)
Um = 250V Uo = 28V Io = 3mA
Co = 0.083uF Lo = 100mH Po = 21mW

wiring diagram

PRG-1802 Frequency Isolation Safety Barrier Wiring Diagram

Outline dimension drawing (mm)

PRG-1802 Frequency Isolation Safety Barrier Dimensions

Outline drawing of PRG-1802 frequency isolated safety barrier

PRG-1802 Frequency isolated safety barrier
Product Category