ECA110A type differential pressure transmitterDetailed product description:

The ECA110A differential pressure transmitter is used to measure the liquid, gas, or vapor level, density, and pressure, and then convert it into a 4-20mADC current signal output. ECA110A can also communicate with the HART275 handheld controller for setting, monitoring, and other purposes.
Functional specifications
output
2-wire system, 4-20mA DC output, digital communication, programmable linear or square root output mode, HART protocol loaded on 4-20mA DC signal.
power supply voltage
10.5~42V DC (working state)
(10.5-30V DC intrinsic safety type)
16.4~42V DC (digital communication, BRAIN and HART protocols)
(16.4~30V DC intrinsic safety type)
Load (when output signal codes are D and E)
0-1335 Ω working state
250-600 Ω digital communication
HART
communication distance
Using multi-core twisted pair cables, the maximum communication distance can reach 1.5km, and the communication distance varies depending on the cable type.
Ambient temperature
-40~85℃(-40~185°F)
-30-80 ℃ (-22-176 ° F) [with LCD meter head]
Liquid contact temperature
-40~120℃(-40~248°F)
Performance Specifications
Reference accuracy for range adjustment
(including linearity, hysteresis, and repeatability starting from zero)
±0.1%~±0.5%
Static pressure influence
L membrane box
± [0.07% range+0.052% range upper limit]/3.4MPa {500psi}
M. H and V membrane boxes
± [0.1% range+0.028% range upper limit]/6.9MPa {1000psi}
Overvoltage effects (M, H, and V bellows)
± 0.03% upper range limit/6.9MPa {2000psi}
Stability (M, H, and V membrane boxes)
± 0.1% range upper limit/60 months