Product name: |
SX-9000D type anti-interference dielectric loss tester
|
|
specification: |
|

Zoom in on the image |
|
Category: |
instrumentation and meters
-- Engineering instruments |
|
Price: |
factory price |
|
Brand: |
Shanghai |
|
Place of Origin: |
China |
|
Available Quantity: |
batch |
|
delivery cycle: |
Spot goods (or inquire by telephone) |
|
| |
Shanghai Beiyuan Industry and Trade Co.,Ltd
+86-21-66770508
+86-13901609058 |
91way@163.com
13901609058(Wechat) |
|
|
|
SX-9000D type anti-interference dielectric loss testerDetailed product description:

The SX-9000D anti-interference dielectric loss tester has added the testing function of a capacitive voltage transformer (CVT), which has the advantages of simple operation, automatic measurement, intuitive reading, no need for conversion, high accuracy, and strong anti-interference ability.
Function and Features
There are multiple measurement methods available, including positive/reverse wiring, internal/external standard capacitors, CVT, and internal/external test voltages for measurement. Positive wiring can measure high voltage dielectric loss.
When measuring a capacitive voltage transformer (CVT), no other external equipment is required, and the internal output self-excited voltage is 6-50V
Built in SF6 standard capacitor, tgδ<0.005%, Less affected by air humidity.
Good anti-interference effect; It can effectively eliminate the influence of strong electric field interference on measurement and is suitable for strong interference field tests in power stations of 500kV and below.
When there is a high voltage short circuit or sudden power outage, the instrument can quickly cut off the high voltage and issue a warning message.
Good measurement repeatability and voltage linearity (measurement accuracy is not affected by voltage)
Integrated structure, moderate weight, easy to carry.
Large screen with backlit Chinese LCD display for information prompt operation, easy to use.
The anti-interference dielectric loss tester comes with a printer to save test data in a timely manner.
Connect the high-voltage cable to the test sample to ensure safety; The instrument is not grounded and the alarm is triggered. The safety measures are complete.
Technical specifications of SX-9000D anti-interference dielectric loss tester
1. Rated working conditions
1.1 Environmental temperature: 0-40 ℃ (When the temperature exceeds 20 ℃± 5 ℃, the change in instrument basic error for every 10 ℃ change shall not exceed 1/2 of the basic error limit.)
1.2 Relative humidity: 30% to 85%
1.3 Power Supply: Voltage: 220V ± 22V, Frequency: 50 ± 1Hz
2. Dimensions: l × b × h, mm: 440 × 330 × 400
3 Weight: Approximately 18kg
4. Power consumption of electronic circuits: not exceeding 40VA
5 Measurement Range:
5.1 Dielectric loss (tg δ): 0-100% resolution 0.0001
5.2 Capacitance (Cx): Minimum resolution of 0.01pF
5.2.1 Internal Connection Method
Test voltage, test sample capacitance
5kV 7.5kV 10kV 1pF~60000PF
1.5kV 2.25kV 3k 10pF~0.35μF
0.5kV 0.75kV 1kV 30pF~1.5μF
5.2.2 External Connection Method
The maximum test voltage for the "external booster" method is 10kV
The maximum test voltage of the "external Cn" method (external high voltage, external standard capacitor) is determined by the standard capacitor and the test subject
Product Decision (Umax=Imax/wC)
The maximum current of the standard circuit is 50mA (In=UwCn)
The maximum current of the test circuit is 2A (Ix=UwCx)

Related Products: