The GS8500-EX series ultra-thin isolated safety barrier uses a customized shell from Phoenix Contact in Germany, with a thickness of only 12.5mm, making it the thinnest product of its kind in the world. In terms of circuit design, the GS8500-EX functional safety isolation barrier uses a new plate type transformer instead of the traditional ring transformer, further enhancing anti-interference performance and consistency of signal coupling. Adopting low-power technology to reduce power consumption. In addition, functional safety technology is introduced in accordance with the IEC 615508 standard during the research and design process to improve product reliability and safety, achieving SIL2 and SIL3 levels. Realize independent power supply from the power terminal and optional power supply from the power bus.
Product performance
Power supply: independent power supply from the power terminal, power supply from the power bus (optional)
Number of channels: One in one out, One in two out, Two in two out
Function: Signal isolation transmission, transmission conversion, distribution, alarm setting
Matching signals and intrinsic safety instruments:
Switch, proximity switch input
Intrinsic safety power output for driving intrinsic safety solenoid valves and indicator lights
Two wire and three wire transmitter inputs (including HART)
Current signal output
Thermal resistance, thermocouple input
GS8500-EX Functional Safety Barrier General Technical Parameters
Power protection: reverse power protection
Safe isolation: 250V, A.C
Insulation strength: 2500V, A.C; 1 minute (local and non local end)
Electromagnetic compatibility: Complies with IEC 61326 "Electromagnetic compatibility of electrical equipment for measurement, control, and laboratory use"
Capacity Requirements Part 1: General Requirements
Compliant with IEC 61326-3-1 "Electromagnetic Requirements for Electrical Equipment for Measurement, Control, and Laboratory Use"
Compatibility Requirements Part 3-1: Safety Related Systems and Expected Execution of Safety Related Functions (Safety Functions)
Immunity requirements for equipment - General occasions
Usage environment:
Installed in a safe environment without explosive gases, and there must be no strong vibrations, impacts, corrosive gases, or dust present in the surrounding environment that can harm product components
Continuous operating temperature: -20 ℃ to+60 ℃
Relative humidity: 10% to 90%
Storage conditions:
Temperature: -40 ℃ to+80 ℃
Relative humidity: 10% to 90%
Structure and Outline Drawing
Instrument structure: German Phoenix mold GS8500 series plastic shell structure
Installation method: In a safe area, DIN35mm standard guide rail
Wiring terminal: pluggable, blue terminal connected to danger side signal, green terminal connected to safety side signal, can be connected
0.5mm ²~2.5mm ² multi bundle or single strand cable
Overall dimensions:
114.5mm×99.0mm×22.5mm(ME22.5) 114.5mm×99.0mm×12.5mm(ME12.5)

GS8500-EX Functional Safety Barrier