HomeYour location:HomePump valve fittingsvalve productsBreathing valve|flame arrester → ZGB-1 new corrugated oil storage tank flame arrester
Column tabs 
Product name: ZGB-1 new corrugated oil storage tank flame arrester
specification: ZGB-1 new corrugated oil storage tank flame arrester
  Zoom Zoom in on the image
Category: Pump valve fittings -- Breathing valve|flame arrester
Column tabs 
Price: factory price
Brand: Shanghai
Place of Origin: China
Column tabs 
Available Quantity: batch
delivery cycle: Spot goods (or inquire by telephone)
tabs
  Shanghai Beiyuan Industry and Trade Co.,Ltd
+86-21-66770508
+86-13916950330

Email 91way@163.com
Wechat 13916950330(Wechat)


ZGB-1 new corrugated oil storage tank flame arresterDetailed product description:Column tabs

The ZGB-1 new corrugated oil storage tank flame arrester is a new product designed by Beijing Design Institute of China Petrochemical Corporation. It has been tested and qualified by Tianjin Fire Science Research Institute of the Ministry of Public Security according to the GB5908-86 standard of the People's Republic of China. The ZGB-1 new corrugated flame arrester is widely used in oil storage tanks to prevent accidental fire from entering the tank and prevent accidents. It is an ideal product for tank fire prevention.

Performance and Characteristics
The ZGB-1 new corrugated oil storage tank flame arrester has a reasonable structure, light weight, corrosion resistance, and qualified explosion resistance performance. It has been tested for 13 consecutive subsonic flame tests and has been able to extinguish fire every time.
Easy to maintain, easy to install, no need to disassemble the breathing valve during inspection. The fire resistance performance is qualified, and there is no tempering phenomenon after 1 hour of fire resistance test.
The flame arrester core is made of stainless steel material, which is corrosion-resistant and easy to clean. The shell water pressure test is qualified.

Corrugated flame arrester American standard flange connection external dimensions: ANSI, API, ASME available for JIS standards

Specification
Installation size (mm)
D2
D
L
H
N-d
2"
Φ120.5
Φ152
two hundred and twenty
two hundred and thirty-five
4×19
3"
Φ152.5
Φ190
two hundred and eighty
two hundred and seventy
4×19
4"
Φ190.5
Φ229
three hundred and twenty-five
two hundred and seventy-five
8×19
6"
Φ241.5
Φ279
four hundred and twenty-five
two hundred and ninety
8×22
8"
Φ298.5
Φ343
four hundred and ninety-five
three hundred and five
8×22
10"
Φ362
Φ406
five hundred and ninety-five
three hundred and twenty
12×25
12"
Φ432
Φ483
six hundred and fifty-five
four hundred and five
12×25

Scope of Application
ZGB-1 new corrugated oil storage tank flame arrester is suitable for pipelines, Class A with a flash point below 28 ℃, oil products, hydrogen oxygen liquefaction, and kerosene, diesel, toluene, crude oil, etc. with a flash point below 60 ℃. It can be used in conjunction with breathing valves or separately on the ventilation pipes of internal floating roof oil tanks and underground oil tanks at refueling stations.

National standard flange connection dimensions for corrugated flame arresters: GB, JB

Specification
Installation size (mm)
D2
D
L
H
N-d
DN50
Φ110
Φ140
two hundred and twenty
two hundred and thirty-five
4×14
DN80
Φ150
Φ185
two hundred and eighty
two hundred and seventy
4×18
DN100
Φ170
Φ205
three hundred and twenty-five
two hundred and seventy-five
4×18
DN150
Φ225
Φ260
four hundred and twenty-five
two hundred and ninety
8×18
DN200
Φ280
Φ315
four hundred and ninety-five
three hundred and five
8×18
DN250
Φ335
Φ370
five hundred and ninety-five
three hundred and twenty
12×18
DN300
Φ395
Φ435
six hundred and fifty-five
four hundred and five
12×23

Maintenance and Repair
In order to ensure the safe use of flame arresters, they should be regularly inspected and maintained.
The flame arrester should be inspected every six months to check whether the flame arrester core is blocked, deformed, corroded, etc.
The blocked fire-resistant layer core should be cleaned thoroughly to ensure that each hole on the core is unobstructed, and any deformed or corroded fire-resistant layer should be replaced.
When reinstalling the fire-resistant layer core, it should be ensured that the joint surface is tight and there is no air leakage.

Materials of components for corrugated flame arresters:

Valve body material
Carbon steel WCB, stainless steel 304, 316
Fire retardant core material
Stainless steel explosion-proof and fire-resistant corrugated plate
Sealing material
Oil resistant asbestos rubber, PTFE tetrafluoroethylene
Environmental temperature ℃
≤480
Nominal pressure (MPa)
0.6~5.0
Explosion proof level
BS5501: IIA, IIB, IIC

ZG2-1 New Ripple Oil Storage Tank Flame Arrestor Dimensions

ZGB-1 new corrugated oil storage tank flame arrester
Product Category