Scope of application
The PK40 series signal isolator is used for adjusting and isolating various signals of field instruments, and converting them into standard signals that can be accepted by computers, DCS, PLCs, or special signals specified by users. This isolator has multiple signal inputs and corresponding multiple isolated signal outputs Input, output, and power supply are fully isolated Strong anti-interference ability, high precision, and rail installation. It has extremely high cost-effectiveness, reliable and stable operation, and can be matched with unit combination instruments and DCS, PLC and other systems. It has a wide range of applications in major projects in industries such as oil fields, petrochemicals, manufacturing, power, metallurgy, etc.
Main technical parameters
1. System transmission accuracy: ± 0.2% × F · S
2. Temperature drift: 25ppm/℃
3. Input impedance: Current: 250 Ω; Voltage: 500K Ω
4. Allowable external load impedance for current output:<600 Ω for current output; Voltage output allows external load>10K
5. Insulation resistance: between the power supply, input, and output, greater than or equal to 100M Ω (500VDC)
6. Input/output/power isolation voltage: ≥ 3000V.dc/min
7. Power supply: DC24V (reverse protection)
8. Working temperature: Industrial standard -20~+70 ℃, relative humidity: 10-90% RH (at 40 ℃)
9. Dimensions: Length x Width x Height: 72mmx87mmx62mm
10. Installation: 35mm standard guide rail card installation
Selection Guide
| Product Design Number |
|
explanation |
| PK-40 |
X |
X |
X |
Multi channel signal isolator |
through the Way number |
two |
|
|
Two channels |
| three |
|
|
three-channel |
| four |
|
|
four-channel |
| five |
|
|
Five channels |
lose enter letter number
|
|
one |
|
1:0-1V |
| two |
|
2:0-5V |
| three |
|
3:1-5V |
| four |
|
4:0-10V |
| five |
|
5:0-10mA |
| six |
|
6:0-20mA |
| seven |
|
7:4-20mA |
lose out letter number
|
|
one |
1:0-1V |
| two |
2:0-5V |
| three |
3:1-5V |
| four |
4:0-10V |
| five |
5:0-10mA |
| six |
6:0-20mA |
| seven |
7:4-20mA |
PK40 series multi-channel signal isolator wiring diagram: