HomeYour location:HomeHigh voltage electrical appliancesHigh voltage isolation switchOutdoor isolation switch → GW5 series outdoor high-voltage isolation switch
Column tabs 
Product name: GW5 series outdoor high-voltage isolation switch
specification: GW5 series outdoor high-voltage isolation switch
  Zoom Zoom in on the image
Category: High voltage electrical appliances -- Outdoor isolation switch
Column tabs 
Price: factory price
Brand: Shanghai
Place of Origin: China
Column tabs 
Available Quantity: batch
delivery cycle: Spot goods (or inquire by telephone)
tabs
  Shanghai Beiyuan Industry and Trade Co.,Ltd
+86-21-66770508
+86-13916500500

Email 91way@163.com
Wechat 13916500500(Wechat)


GW5 series outdoor high-voltage isolation switchDetailed product description:Column tabs
The GW5 series outdoor high voltage isolation switch is a three-phase AC 50HZ outdoor high voltage electrical device used for voltage and no-load division circuits.  
The GW5 series outdoor high-voltage isolation switches are divided into two types based on their external insulation capacity: ordinary type and pollution resistant type. Both types can be equipped with grounding switches, which can be single grounded or double grounded. Grounding switches are further divided into Type I and Type II based on their ability to withstand the thermal effects of short-circuit currents.

Structure:
The GW5 series outdoor high-voltage isolation switch is equipped with a CS17 manual operating mechanism, which is equipped with an electromagnetic lock and an interlocking board to achieve interlocking between the main switch blade of the isolation switch and the grounding switch.


Product Model Type
Parameter Data
Project Name: Item

GW5-40.5D
D(W)

GW5-72.5D
D(W)

GW5-126D
D(W)

Rated Voltage KV
forty point five
seventy-two point five
one hundred and twenty-six

Rated current A

630 1250 1600
Rated short time withstand current (RMS) kA
20 31.5
Rated short circuit suspected time S
four
Rated peak withstand current (peak) kA
50 80
Rated mechanical load of terminal (axial)
five hundred
five hundred
seven hundred and fifty

Rated short-time power frequency withstand voltage (effective value)
Rated short-time power frequence   
withstand voltage(rms) kV

to the ground
to each

eighty-five
one hundred and forty
one hundred and eighty-five

fracture
between breaks

one hundred and ten
one hundred and sixty
two hundred and ten

Rated lightning impulse withstand voltage (peak)
Lightning impulse withstand
voltage(peak) KV

to the ground
to each

one hundred and eighty-five
three hundred and twenty-five
four hundred and fifty

fracture
between breaks

two hundred and fifteen
three hundred and seventy-five
five hundred and twenty

Rated parameters of grounding switch assembled with isolation switch
Technical data of earthing switch is connected with disconnector

Type I
Type

4s rated short-time withstand current (effective value)
4s short time withstand current(rms) kA

eight

Rated peak withstand current (peak)
Peak withstand current(peak) kA

twenty

Type II
TypeⅡ

1-second rated short-time withstand current (effective value)
1s short time withstand current(rms) kA

20 31.5

Rated peak withstand current (peak)
Peak withst and current(peak) kA

50 80

GW5 series outdoor high-voltage isolation switch
  • Related product tags  Related Products:
Product Category
All product information on this website is translated by Baidu machine translation, which may not be completely accurate and is only for reference