FN12-12RD High voltage load switchDetailed product description:Column tabs
FN12-12D/630-50 indoor AC high voltage load switch (hereinafter referred to as FN12-12D load switch) is a three-phase high voltage starting device with a rated voltage of 12kV and a rated frequency of 50Hz. It is used for switching load current, closed-loop current, no-load transformer and cable charging current, and switching short-circuit current. Load switches equipped with grounding switches can withstand short-circuit currents.
The FN12-12RD/125-31.5 AC high voltage load starting fuse combination (hereinafter referred to as FN12-12 (R) D combination) is an indoor high voltage switchgear that combines the FN12-12RD load switch with the S-port LAJ (XRNT port-10) high voltage current limiting fuse. It can disconnect any current up to the short-circuit current; The load switch disconnects the working current, the fuse disconnects the short-circuit current, and jointly disconnects any current between the working current and the full short-circuit current. At the same time, the fuse causes the load switch to open through its impact.

Scope of application
The FN12-12RD/load switch FN12-12RD combination electrical device is mainly used for load control and short-circuit protection in urban distribution stations and industrial electrical equipment powered by three-phase ring networks or terminals. Due to the more reliable protective effect of composite appliances on electrical equipment such as transformers than using circuit breakers, they are particularly suitable for ring networks, radiation replacement units, and box type substations.

Normal working environment
Using ambient air temperature: upper limit+40 ℃, lower limit -25 ℃;
Altitude not exceeding 1000M;
Relative humidity, with a daily average not exceeding 95% and a monthly average not exceeding 90%;
The surrounding air should not be significantly polluted by corrosive or flammable gases and water vapor;
No frequent vigorous exercise;
Pollution resistance level: Level II;
If the usage conditions exceed the above regulations, it shall be determined through consultation between the user and the manufacturer.

Technical parameters and performance of FN12-12RD high-voltage load switch

serial number

project

unit

FN12-12D/630

FN12-12RD/125

one

rated voltage

kV

twelve

two

rated frequency

Hz

fifty

three

rated current

A

six hundred and thirty

one hundred and twenty-five

four

Lightning impulse withstand voltage

kV

Ground and phase to phase 75, isolation and disconnection 85

five

1-minute power frequency voltage

kV

Ground and phase 42, isolation and disconnection 48

six

Rated thermal stability current

kA

20(4S)

seven

Rated dynamic stable current

kA

fifty

eight

Rated closing current (peak value)

kA

fifty

fifty

nine

Rated short-circuit breaking current (expected value)

kA

thirty-one point five

ten

Maximum 1 ㎡· t when temporarily disconnecting current

A²S

According to the characteristic curve of the fuse

eleven

Minimum breaking current

kA

According to the characteristic curve of the fuse

twelve

Rated transfer current

kA

one point five

thirteen

Maximum breaking current (reference value)

kA

one point eight

fourteen

Disconnect the capacity of the no-load transformer

kva

one thousand two hundred and fifty

fifteen

Rated cable charging current

A

ten

sixteen

Rated active load current breaking times

time

>100

seventeen

Rated active load current switch opening time

S

>0.06

eighteen

Grounding switch thermal stability current

kA

20(2S)

20(2S)

nineteen

Stable current (peak value) of grounding switch

kA

fifty

fifty

twenty

Electric motor operating power supply voltage

V

AC/DC 100, 220


Mechanical characteristic parameters of FN12-12RD high-voltage load switch

serial number

project

unit

FN12-12RD/630

FN12-12RD/125

one

Total travel of moving contact

mm

200 +8 -2

two

Intermediate distance between phases (before energy storage of the mechanism)

mm

210±3

three

Moving contact overtravel

mm

40±2

four

Auxiliary hoe opening distance

mm

one hundred and fifty

five

Synchronization of three-phase opening and closing

ms

<3

six

Just divided speed

ms

>2.8

>2.8

seven

Just closed speed

ms

>3.8

eight

Distance between metal valve and conductive tube

mm

>125

nine

Grounding switch fracture distance

mm

>150

ten

main circuit resistance

μΩ

<120

<300

eleven

Maximum operating force distance

Nm

<160

Outline and Installation Dimensional Drawing of FN12-12RD High Voltage Load Switch