| Product name: | FKRN16-12D High voltage load switch | ||||||
| specification: | ![]() |
||||||
| Category: | High voltage electrical appliances -- Indoor high-voltage load switch | ||||||
| Price: | factory price | ||||||
| Brand: | Shanghai | ||||||
| Place of Origin: | China | ||||||
| Available Quantity: | batch | ||||||
| delivery cycle: | Spot goods (or inquire by telephone) | ||||||
|
|||||||
|
serial number |
project |
unit |
FKN16-12D/630 |
FKRN16-12D/125 |
|
one |
rated voltage |
kV |
twelve | |
|
two |
rated frequency |
Hz |
fifty | |
|
three |
rated current |
A |
six hundred and thirty |
one hundred and twenty-five |
|
four |
Lightning impulse withstand voltage |
kV |
Ground and phase to phase 75, isolation and disconnection 85 | |
|
five |
1-minute power frequency voltage |
kV |
Ground and phase 42, isolation and disconnection 48 | |
|
six |
Rated thermal stability current |
kA |
20(4S) | |
|
seven |
Rated dynamic stable current |
kA |
fifty | |
|
eight |
Rated closing current (peak value) |
kA |
fifty |
fifty |
|
nine |
Rated short-circuit breaking current (expected value) |
kA |
thirty-one point five | |
|
ten |
Maximum 1 ㎡· t when temporarily disconnecting current |
A²S |
According to the characteristic curve of the fuse | |
|
eleven |
Minimum breaking current |
kA |
According to the characteristic curve of the fuse | |
|
twelve |
Rated transfer current |
kA |
one point five | |
|
thirteen |
Maximum breaking current (reference value) |
kA |
one point eight | |
|
fourteen |
Disconnect the capacity of the no-load transformer |
kva |
one thousand two hundred and fifty | |
|
fifteen |
Rated cable charging current |
A |
ten | |
|
sixteen |
Rated active load current breaking times |
time |
>100 | |
|
seventeen |
Rated active load current switch opening time |
S |
>0.06 | |
|
eighteen |
Grounding switch thermal stability current |
kA |
20(2S) |
20(2S) |
|
nineteen |
Stable current (peak value) of grounding switch |
kA |
fifty |
fifty |
|
twenty |
Electric motor operating power supply voltage |
V |
AC/DC 100, 220 | |
Mechanical characteristic parameters
|
serial number |
project |
unit |
FKN16-12D/630 |
FKRN16-12D/125 |
|
one |
Total travel of moving contact |
mm |
200 +8 -2 | |
|
two |
Intermediate distance between phases (before energy storage of the mechanism) |
mm |
210±3 | |
|
three |
Moving contact overtravel |
mm |
40±2 | |
|
four |
Auxiliary hoe opening distance |
mm |
one hundred and fifty | |
|
five |
Synchronization of three-phase opening and closing |
ms |
<3 | |
|
six |
Just divided speed |
ms |
>2.8 |
>2.8 |
|
seven |
Just closed speed |
ms |
>3.8 | |
|
eight |
Distance between metal valve and conductive tube |
mm |
>125 | |
|
nine |
Grounding switch fracture distance |
mm |
>150 | |
|
ten |
main circuit resistance |
μΩ |
<120 |
<300 |
|
eleven |
Maximum operating force distance |
Nm |