| Product name: | YA-3 Type Intrinsic Safety Explosion proof Pressure Transmitter | ||||||
| specification: | ![]() |
||||||
| Category: | instrumentation and meters -- Pressure transmitter | ||||||
| Price: | factory price | ||||||
| Brand: | Shanghai | ||||||
| Place of Origin: | China | ||||||
| Available Quantity: | batch | ||||||
| delivery cycle: | Spot goods (or inquire by telephone) | ||||||
|
|||||||
|
Main technical indicators | |||
|
measurement range |
gauge pressure | 0 ~ 17,35 | kPa |
| 0- 0.1 ~ 35 | MPa | ||
| absolute pressure | 0- 0.1 ~ 35 | MPa | |
|
output signal |
4-20mA (two-wire system) | ||
|
accuracy class |
0.2; zero point five | ||
|
basic error |
±0.2; ±0.5 | %F.S | |
|
return stroke error |
±0.16; ±0.4 | %F.S | |
|
Working temperature range |
-10~+70 | ℃ | |
|
Temperature compensation range |
0~+70 | ℃ | |
|
Storage temperature range |
-25~+125 | ℃ | |
|
Zero temperature influence |
±0.02 | %F.S/ ℃ | |
|
Output temperature impact |
±0.03 | %F.S/ ℃ | |
|
excitation voltage |
12~36 | VDC | |
|
insulation resistance |
one thousand | MΩ/100VDC | |
|
Safety overload rate |
two hundred | %F.S | |
| Electrical connection method | ||||
| connection method | Plug socket number | Wire color | ||
| Input (power) positive terminal | one | red | ||
| Output signal positive terminal | two | Blue | ||
| If the plug socket number or wire color changes, please refer to the sensor calibration certificate for accuracy. | ||||

YA-3 intrinsically safe explosion-proof pressure transmitter