Overview
The FDGE8 discharge coil is suitable for power systems with a rated frequency of 50Hz or 60Hz and a rated voltage of 10kV and below. It is connected in parallel with a high-voltage parallel capacitor bank. When the capacitor bank is disconnected from the system, it can reduce the remaining voltage on the capacitor bank to a safe voltage within 5 seconds. During normal operation, the secondary winding can serve as a voltage indicator. If the user has special requirements, the residual voltage winding can also be included to provide relay protection.
The product complies with the technical specifications for ordering discharge coils for voltage parallel capacitors (DL/T 653-1998).
Model and its meaning

Normal usage conditions
Installation location: Indoor.
Environmental temperature: maximum temperature of 40 ℃; Minimum temperature -5 ℃; The daily average temperature does not exceed 30 ℃.
Atmospheric conditions: There is no severe pollution in the atmosphere.
Technical parameters of FDGE8 discharge coil
|
Product Model |
rated voltage ratio (kV) |
Accuracy level or combination of accuracy levels |
rated output (VA) |
discharge capacity (Mvar) |
Rated insulation level (kV) |
|
FDGE8/6.6/√3-1.7-1 |
6.6/√3/0.1 |
0.2(0.5) |
20(50) |
one point seven |
7.2/32/60 |
|
6.6/√3/0.1/0.1/3 |
0.2(0.5)/6P |
20(50)/100 |
|
FDGE8/7.2/√3-1.7-1
|
7.2/√3/0.1 |
0.2(0.5) |
20(50) |
|
7.2/√3/0.1/0.1/3 |
0.2(0.5)/6P |
20(50)/100 |
|
FDGE8/11/√3-1.7-1 |
11/√3/0.1 |
0.2(0.5) |
20(50) |
12/42/75 |
|
11/√3/0.1/0.1/3 |
0.2(0.5)/6P |
20(50)/100 |
|
FDGE8/12/√3-1.7-1 |
12/√3/0.1 |
0.2(0.5) |
20(50) |
|
12/√3/0.1/0.1/3 |
0.2(0.5)/6P |
20(50)/100 |
Rated insulation level: 0.5/3kV
Structure and Characteristics
This series of discharge coils is a semi enclosed epoxy casting type, with the iron core made of high-quality silicon steel sheets stacked together. The casting body contains a cylindrical concentric combination of primary and secondary coils. There are grounding bolts and four mounting holes for installation on the bottom clamp of the product.
Outline drawing and installation dimensions of FDGE8 discharge coil

Ordering Instructions
Please provide the following parameters when placing an order:
Product model.
The rated voltage is in kV.
Accurate level combination and rated output VA.
Discharge capacity Mvar.
The altitude of the environment is m.
Note: If users have special requirements, they can negotiate with our company to determine.