Product Description
PRG-1000 is a passive detection end and operation end universal isolation safety barrier. This product does not require an auxiliary power supply, and users can choose either the detection end or the operation end of the dual channel circuit as needed, without the need for intrinsic safety grounding, making it extremely convenient to use. The detection end is connected to a two-wire transmitter, and the operation end is connected to a valve positioner and an electrical converter.
Main technical specifications
Model naming convention:
PRG-1000- Port ⇒ 1: Single channel 2: Dual channel
Power supply voltage: 24V circuit power supply
Internal power consumption of safety barrier: 200mW (including internal load resistance)
Detection end method (dangerous side)
Input current: 4-20mA
Distribution voltage of transmitter:
Maximum voltage ≤ 25V (30V circuit supply, 4mA output) Minimum voltage ≥ 14V (24V circuit supply, 20mA output)
Internal load impedance of distribution power supply: 302 Ω
Output signal: 4-20mA (safety side)
Operation mode (dangerous side)
Output current: 4-20mA
Voltage drop: 9V (with a current of 20mA and an internal load resistance of 302 Ω)
Input current: 4-20mA (safe side)
performance metrics
Insulation strength: 2500Vac/1 minute for local/non local ends
Output accuracy: 0.1% F.S (operating mode)
0.2% F.S (detection method)
Temperature drift: ± 0.01%/℃
Working temperature: -20 to+60 ℃
Current humidity: 35% to 85% RH
Storage temperature: -40 ℃ to+80 ℃
Structure and external dimensions
Product structure: 35mm guide rail card mounting
ABS shell material
Plug in terminal
Dimensions: 22.5 × 114.5 × 99 (mm)
Whole machine weight: 120g
Product Features
No need for independent power supply, universal detection and operation, in compliance with EMC standards
installation site
The surrounding air should not contain any medium that corrodes chromium, nickel, and silver coatings
Applicable on-site and equipment
Zone 0, Zone 1, Zone 2, Hazardous Zones IIA, IIB, and IIC
Channel 1: Valve positioner, electric/pneumatic converter
Channel 2: Two wire transmitter
Safety and Explosion proof Certification Parameters
National Quality Supervision and Inspection Center for Explosion proof Electrical Products (CQST)
Explosion proof mark: [EXia] (IIC)
Authentication parameters: terminals (5.6 and 7.8)
Uo :28V Io :93mA
Po :675mW Um:250V
IIC:Co=0.05uF, Lo=0.45mH
IIB:Co=1.65uF, Lo=1.3mH
IIA:Co=3.3uF, Lo=2.8mH
wiring diagram

Outline dimension drawing (mm)