Product Description
PRG-1500/1501 thermocouple/millivolt isolation safety barrier converts on-site thermocouple/millivolt signals into one or two standard 4mA~20mADC current signals for isolation and transmission to the safety side. This is an intelligent safety barrier with cold end automatic compensation function. The thermocouple millivolt model, range, etc. can be set through a computer or setter
Main technical specifications
Power supply voltage: 20V-35Vdc power supply
Number of channels: PRG-1500 single channel PRG-1501 single input dual output
Power consumption: approximately 1.8W (24V power supply, 20mA output)
Input signal type: thermocouple millivolt signal
Input signal range: corresponding thermocouple measurement range
Signal range: specified or self configured by the user when placing an order
Output signal range: 4mA~20mAdc
Allowable output load capacity: 0-650 Ω
Alarm indication: low range alarm, L alarm indicator light on
High range alarm, H alarm indicator light on
Fault alarm, L and H alarm indicators light up simultaneously
Cold end compensation accuracy: ± 1 ℃ (-40 ℃~85 ℃)
performance metrics
Insulation strength: 2500Vac/min between intrinsic safety end and non intrinsic safety end, 1000Vac/min between non intrinsic safety end and non intrinsic safety end
Output accuracy: 0.1% F.S
Temperature drift: 0.01% F.S/℃
Working temperature: -20 ℃~+60 ℃
Relative humidity: 35% to 85% RH
Storage temperature: -40 ℃ to+80 ℃
Structure and external dimensions
Product structure: 35mm guide rail card mounting,
ABS shell material,
Plug in terminal
Dimensions: 22.5 × 114.5 × 99 (mm)
Whole machine weight: 150g
Product Features
IIC explosion-proof rating, compliant with EMC standards, wide range power supply, pluggable cold end compensation terminal, configurable settings (thermocouple type, range)
installation site
The surrounding air should not contain any medium that corrodes chromium, nickel, and silver coatings
Applicable on-site and equipment
J. K, T, E, S, B, N, R thermocouples; Millivolt signal
Safety and Explosion proof Certification Parameters
National Quality Supervision and Inspection Center for Explosion proof Electrical Products (CQST)
Explosion proof mark: [EXia] (IIC)
Authentication parameters: Terminal (9.10)
Um = 250V Uo = 8.4V Io = 4mA
Co = 6.8uF Lo = 100mH Po = 8.4mW
PRG-1500/1501 Thermocouple/Millivolt Isolation Safety Barrier Wiring Diagram

Outline dimension drawing (mm)