FZN23-12 High voltage vacuum load switchDetailed product description:Column tabs
FZN23-12 (D)/630 indoor vacuum load switch and FZRN23-12 (D)/125 vacuum load switch fuse combination are suitable for high-voltage switchgear with three-phase AC 50Hz and 12kV. They are used for breaking load current and closing short-circuit protection. The combination can also break short-circuit current for short-circuit protection. They are the main components for controlling and protecting power equipment such as transformers, cables, and overhead lines.

2、 FZN23-12 High Voltage Vacuum Load Switch Main Types
FZN23—12/630
Vacuum load switch
FZN23—12D/630
Vacuum load switch with grounding switch
FZRN23—12/125
Vacuum load switch fuse combination device
FZRN23-12D/125
Vacuum load switch fuse combination with grounding switch

3、 Technical parameters

name
unit
load switch
combined electrical apparatus
rated voltage
kV
twelve
twelve
rated current
A
six hundred and thirty
one hundred and twenty-five
Rated active load breaking current, rated closed-loop breaking current
A
six hundred and thirty
Rated short-time withstand current (2S)
kA
twenty
Rated short-circuit closing current
kA
fifty
Rated peak withstand current
kA
fifty
Rated cable charging breaking current
A
ten
Rated open circuit no-load transformer
kVA
one thousand and six hundred
one thousand and six hundred
Rated breaking and handover current
A
two thousand
Rated short-circuit breaking current of fuse
kA
31.5 (expected value)
1-minute power frequency withstand voltage (phase to phase, ground/isolation fracture)
kV
42/48
42/48
Lightning impulse withstand voltage (phase to phase, ground/isolated fracture)
kV
75/85
75/85
mechanical life
time
five thousand
five thousand
Electric operating voltage
V
AC/DC 220V
Rated voltage of shunt release
V
AC/DC 220V


4、 Outline drawing of switch and cabinet door opening diagram

Installation dimension diagram of FZN23-12 high-voltage vacuum load switch

5、 Ordering Notice
Product model/quantity:
Installation method: (formal, side mounted, inverted)
Operation panel position: (right, left, L size)
Operation mode: (manual, electric)
Special requirements: (shunt release, auxiliary switch)
Other requirements: (mode of transportation, delivery time)

FZN23-12 High voltage vacuum load switch
Product Category
All product information on this website is translated by Baidu machine translation, which may not be completely accurate and is only for reference