FKN12-12 series indoor high-voltage load switchDetailed product description:Column tabs
Overview

FN12-12D/630-20 indoor AC high voltage load switch (hereinafter referred to as FN12-12D load switch) is a three-phase high voltage switchgear with a rated voltage of 12KV and a rated frequency of 50Hz. It is used for switching load current, closed-loop current, no-load transformer and cable charging current, and short-circuit current. Load switches equipped with grounding switches can withstand short-circuit currents.

The FN12-12D. R/100-31.5 indoor AC high voltage load switch fuse combination (hereinafter referred to as FN12-12D. R combination) is an indoor high voltage switchgear that combines the FN12-12D load switch with the S □ LAJ-12 (XRNT □ -12) high voltage current limiting fuse. It can reliably disconnect any current up to the short-circuit current: load switch disconnects the working current, fuse disconnects the short-circuit current, and jointly disconnects any overcurrent between the working current and the full short-circuit current, while the fuse opens the load switch through its impactor.

Normal working environment
1. Surrounding air temperature: upper limit+40 ℃, lower limit -25 ℃.
2. The altitude is 1000m and below.
3. Relative humidity: Monthly average not exceeding 90%, daily average not exceeding 95%.
4. The surrounding air should not be significantly polluted by corrosive or flammable gases, as well as steam gases.
5. No frequent vigorous exercise.
6. Pollution resistance level: Level II.
If the usage conditions exceed the above regulations, they shall be determined through consultation between the user and the manufacturer.

Technical parameters and performance of FKN12-12 series indoor high-voltage load switch

serial number project unit FN12-12D/630-20 FN12-12D.R/100-31.5
one rated voltage kV twelve
two rated frequency Hz fifty
three rated current A six hundred and thirty one hundred
four Lightning impulse withstand voltage kV Ground and phase to phase 75, isolated and disconnected 85
five 1-minute power frequency withstand voltage kV To ground and phase 42, isolate and disconnect 48
six Rated thermal stability current kA 20(4S)
seven Rated dynamic stable current kA fifty
eight Rated closing current (peak value) kA fifty
nine Rated short-circuit breaking current kA thirty-one point five
ten Rated transfer current kA one point five
eleven Maximum breaking current (reference value) kA one point eight
twelve Disconnect the capacity of the no-load transformer Kva one thousand two hundred and fifty
thirteen Rated cable charging current A ten
fourteen Rated active load current breaking times time >100
fifteen The time when the impactor triggers the load switch to open S >0.06
sixteen Grounding switch thermal stability current kA 20(2S) 20(2S)
seventeen Grounding switch thermal stability current (peak) kA fifty fifty
eighteen Electric motor operating power supply voltage V AC220、DC48

·Mechanical characteristic parameters

serial number project unit FN12-12D/630-20 FN12-12D.R/100-31.5
one Auxiliary contact opening distance mm >155
two Synchronization of three-phase opening and closing ms <3
three Just divided speed m/s >2.8 2.80+0.4
four Just closed speed m/s >3.8
five Grounding switch fracture distance mm 145 ± 5
six main circuit resistance μΩ <120 <300
seven Maximum operating force distance N.m <160 <180

·Main technical parameters of FKN12-12 series indoor high-voltage load switch

serial number Model number Rated current for melting (A) Capacity of transformer (kVA)
UK model National standard model
one SDLAJ-12 XPNT□-12 sixteen 100,125,160
two twenty two hundred
three twenty-five two hundred and fifty
four thirty-one point five three hundred and fifteen
five forty four hundred
six SFLAJ-12 fifty five hundred
seven sixty-three 630,800
eight eighty one thousand
nine SSLAJ-12 one hundred one thousand two hundred and fifty
ten SKLAJ-12 one hundred and twenty-five one thousand and six hundred


·FKN12-12 series indoor high-voltage load switch appearance and installation dimension diagram

FKN12-12 series indoor high-voltage load switch appearance and installation dimensions

FKN12-12 series indoor high-voltage load switch