Overview
The ZFN22-12 series indoor high-voltage vacuum load switch is a self-developed product based on the FN5 type switch. It is mainly suitable for use in power grids with a rated voltage of 12KV and three-phase AC 50Hz, as a means of breaking load current and switch short-circuit current. The product retains the compact structure and easy installation and use of FN5 switch, and is equipped with a novel dedicated motor to form manual energy storage, closing, manual opening, and electric energy storage. The closing and opening functions of the switch are the preferred products for the new ring network design, and also provide the best solution for directly replacing vacuum load switches with original FN5 switch ring network cabinets.
Environmental conditions for use
1. Environmental temperature: upper limit+40oC, lower limit -25oC
2. Relative humidity: daily average value not exceeding 95%; Monthly average value ≥ 95%
3. The altitude shall not exceed 100mm;
4. There is no risk of fire, explosion, serious pollution, chemical byproducts, or places with severe vibrations.
ZFN22-12 series indoor AC high voltage load switch model meaning

Technical parameters of ZFN22-12 series indoor AC high voltage load switch
| serial number |
name |
unit |
parameter |
| one |
rated voltage |
KV |
twelve |
| two |
rated frequency |
Hz |
fifty |
| three |
rated current |
A |
six hundred and thirty |
| four |
Rated closed-loop breaking current |
A |
six hundred and thirty |
| five |
Rated Active load breaking current |
A |
six hundred and thirty |
| six |
5% rated active load breaking current |
A |
thirty-one point five |
| seven |
Rated cable charging breaking current |
A |
ten |
| eight |
Rated no-load transformer breaking current |
|
1250KVA transformer no-load current |
| nine |
Rated short-circuit closing current |
KA |
fifty |
| ten |
Rated short-circuit peak withstand current |
KA |
fifty |
| eleven |
4S rated thermal stability current |
KA |
twenty |
| twelve |
Rated transfer current |
A |
three thousand one hundred and fifty |
| thirteen |
1-minute power frequency withstand voltage |
KA |
forty-two |
| fourteen |
Lightning impulse withstand voltage (peak value) |
KA |
seventy-five |
| fifteen |
Mechanical lifespan |
time |
one thousand |
Technical specifications
| serial number |
name |
unit |
parameter |
| one |
contact gap |
mm |
8+1 |
| two |
Contact overtravel |
mm |
3±1 |
| three |
Three phase asynchronous opening and closing |
ms |
≤2 |
| four |
Bouncing time of closing contact |
ms |
≤2 |
| five |
Closing speed |
m/s |
0.6±0.2 |
| six |
Opening speed |
m/s |
1±0.2 |
| seven |
Main circuit resistance |
μΩ |
<150 |
| eight |
Opening time |
s |
>0.06 |
| nine |
Interphase center distance |
mm |
210±0.2 |
Outline drawing

1. Terminal introduction 2. Fixed screw hole 3. Isolation switch 4. Vacuum tube 5. Switch spindle 6. Impactor 7. Grounding knife shaft 8. Safety 9. Cabinet frame 10. Terminal extraction