| Product name: | YWK-150 type pressure controller | ||||||
| specification: | ![]() |
||||||
| Category: | instrumentation and meters -- pressure controller | ||||||
| Price: | factory price | ||||||
| Brand: | Shanghai | ||||||
| Place of Origin: | China | ||||||
| Available Quantity: | batch | ||||||
| delivery cycle: | Spot goods (or inquire by telephone) | ||||||
|
|||||||
|
serial number |
Setting value adjustment range MPa |
Switching difference not greater than MPa |
Setting value error MPa |
repeatability error MPa |
Remark |
|
one |
-0.1……0 |
zero point zero zero six five |
±0.004 |
zero point zero zero two |
Controlled medium
Brass 1Cr18Ni9Ti stainless steel Nitrile rubber No corrosive effect |
|
two |
0……0.1 |
zero point zero zero six |
±0.004 |
zero point zero zero two | |
|
three |
0……0.2 |
zero point zero one |
±0.008 |
zero point zero zero four | |
|
four |
0……0.3 |
zero point zero two five |
±0.012 |
zero point zero zero six | |
|
five |
0……0.5 |
zero point zero three |
±0.02 |
zero point zero one | |
|
six |
0……0.8 |
zero point zero seven |
±0.032 |
zero point zero one six | |
|
seven |
0……1 |
zero point zero seven five |
±0.04 |
zero point zero two | |
|
eight |
0……1.5 |
zero point one |
±0.06 |
zero point zero three | |
|
nine |
0……2 |
zero point one two |
±0.08 |
zero point zero four | |
|
ten |
0……3 |
zero point one five |
±0.12 |
zero point zero six | |
|
eleven |
0……4 |
zero point two five |
±0.16 |
zero point zero eight |
Adjustment of Setting Values:
The steps for adjusting the set value of the pressure controller are illustrated as follows:
[Example]: Select a controller with a specification of 0-0.8MPa, and require the pressure to rise to 0.4MPa to send a contact signal. The operation steps are as follows:
1. Loosen the fastening screw
2. Add pressure to 0.4 MPa, which can be read from a standard pressure gauge.
3. Rotate the set value adjustment nut clockwise until the switch contact switches at 0.4MPa.
4. Adjust the pressure of the pressure calibrator to fluctuate back and forth around 0.4 MPa, and check whether the contact switching value is 0.4 MPa when the pressure rises,
This value is the upper switching value to be set, and its corresponding lower switching value should be 0.4MPa minus the switching difference of 0.04MPa (about),
That is around 0.36MPa.
Appearance and installation dimensions:
Notes:
When opening the controller cover, do not turn the internal screws or manipulate the internal parts.
The controller is set to the lower switching value. The adjustment range of the set value refers to the adjustment range of the down switching value.
Do not exceed the maximum allowable pressure during debugging.
The surrounding environment should be free of corrosive gases.
The controller is guaranteed to be used for 18 months from the date of leaving the factory. If it is a product quality issue, it is responsible for timely repair or replacement.