The ZFN21-12D/T630-20 indoor high-voltage vacuum load switch is a three-phase AC 50Hz indoor high-voltage switchgear suitable for distribution systems with a rated voltage of 12kV. The ability of switchgear to close, carry, disconnect loads and overload currents; It can also disconnect and close no-load long lines, no-load transformers, and capacitors.
ZFN21-12DR/T125-31.5 indoor high-voltage vacuum load switch - fuse combination electrical device, is composed of this load switch and fuse, and has protection function in addition to the above functions.
·Environmental conditions for use
1. Surrounding air temperature:+40 ℃ -10 ℃;
2. Altitude not exceeding 1000m;
3. Relative humidity: no more than 90% in indoor areas (+25 ℃);
4. In an environment without conductive dust;
5. Objects without corrosive gases that damage metals and insulation;
6. Places without severe vibrations and impacts;
7. In an environment without the danger of combustion and explosion.
Technical parameters of FZN21-12D/T630-20 indoor high-voltage vacuum load switch
1. Main technical parameters of load switch:
| serial number |
project |
unit |
numerical value |
| one |
rated voltage |
kV |
twelve |
| two |
rated frequency |
Hz |
fifty |
| three |
rated current |
A |
six hundred and thirty |
| four |
Rated Active load breaking current |
A |
six hundred and thirty |
| five |
Rated closed-loop breaking current |
A |
six hundred and thirty |
| six |
5% rated active load breaking current |
A |
thirty-one point five |
| seven |
Rated cable charging breaking current |
A |
ten |
| eight |
Rated no-load transformer capacity |
kVA |
one thousand two hundred and fifty |
| nine |
1-minute power frequency withstand voltage: (vacuum break, phase to phase, relative ground/isolation break) |
kV |
42/48 |
| ten |
Lightning impulse withstand voltage: (vacuum break, phase to phase, relative ground/isolation break) |
kV |
75/85 |
| eleven |
Rated short-time withstand current (thermal stability) |
kA/S |
20/4 |
| twelve |
Rated peak withstand current (thermal stability) |
kA |
five |
| thirteen |
Rated short-circuit closing current |
kA |
fifty |
| fourteen |
Rated current breaking times |
time |
ten thousand |
| fifteen |
mechanical life |
time |
ten thousand |
| sixteen |
Allowable wear thickness of vacuum arc extinguishing chamber contacts |
mm |
two |
| seventeen |
Manual operation force distance |
Nm |
≤200 |
2. Main technical parameters of FZN21-12D/T630-20 indoor high-voltage vacuum load switch combination electrical device:
| serial number |
project |
unit |
numerical value |
| one |
rated voltage |
kV |
twelve |
| two |
rated frequency |
Hz |
fifty |
| three |
Maximum rated current of fuse |
A |
one hundred and twenty-five |
| four |
Rated breaking and handover current |
A |
three thousand one hundred and fifty |
| five |
The opening time of the switch triggered by the fuse |
ms |
40±5 |
| six |
Rated short-circuit breaking current (effective value) |
kA |
thirty-one point five |
| seven |
Rated short-circuit closing current (peak) |
kA |
fifty |
| eight |
1-minute power frequency withstand voltage: (vacuum break, phase to phase, relative ground/isolation break) |
kV |
42/48 |
| nine |
Lightning impulse withstand voltage: (vacuum break, phase to phase, relative ground/isolation break) |
kV |
75/85 |
| ten |
Fuse impactor output ± energy |